Message Overview:
Fault Message:
GEN1 [FIELD +VE TO GROUND]
Fault Code:
2421134LPS
Associated CAS:
| Reporting LRU: | Generator Control Unit (GCU) 1 |
| System Description: | 24-21-00 |
| Schematic Diagram: | 24-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-21-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Generator 1 has tripped off-line or will not come on-line and 'GEN 1 FAIL' CAS message is posted.
Possible Causes:
- Generator Control Unit (GCU) 1 (A56)
- Variable Frequency Generator (VFG) 1 (G1)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only). The GCU NVMs can only be downloaded at position #2 or #3.
Quick Links:
| Removal of the Variable Frequency Generators (VFG) | AMM 24-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Variable Frequency Generators (VFG) | AMM 24-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Disconnect GCU 1 connector A56P1 and VFG 1 connector G1P1. Perform a continuity check as follows:
From To Result A56P1-J Ground - If there is continuity, repair defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A56P1-J G1P1-H - If there is continuity, continue with next step.
- If there is no continuity, repair defective wiring as required and do close out.
- Swap GCU 1 with GCU 2 (physically or using the GCU patch cable). Is the fault still present?
- If YES, continue with next step.
- If NO, replace GCU 1 and do close out.
- Replace VFG 1.
- Do close out.