Message Overview:
Fault Message:
GEN2 FIELD -VE TO GROUND FAULT
Fault Code:
2422102LPS
Associated CAS:
| Reporting LRU: | Variable Frequency Generator (VFG) 2 |
| System Description: | 24-21-00 |
| Schematic Diagram: | 24-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-21-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Variable Frequency Generator (VFG) 2 has tripped off-line or will not come on-line. There is a short circuit to ground at the field negative of the No. 2 main generator.
Possible Causes:
- Generator Control Unit (GCU) 2 (A57)
- Variable Frequency Generator (VFG) 2 (G2)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
NOTE: A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only). The GCU NVMs can only be downloaded at position #2 or #3.
Quick Links:
| Removal of the Variable Frequency Generators (VFG) | AMM 24-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Variable Frequency Generators (VFG) | AMM 24-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap GCU 2 with GCU 3 (physically or using the GCU patch cable).
NOTE: Use PMAT to monitor the fault on GCU. - Disconnect connector GCU No. 2 (A57P1) and VFG No.2 (G2P1). Perform wiring checks (continuity = failure) as follows:
From To Result G2P1-B Ground - If wiring checks are not good, repair the defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace VFG 2.
NOTE: Check if G2J1-B (VFG side) is shorted to ground to confirm VFG/connector failure. - Do close out.