Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

06/25/19

Message Overview:

Fault Message:

GEN2 DELTA CURRENT FAULT

Fault Code:

2422118LPS

Associated CAS:

GEN 2 FAIL
(Advisory)

Reporting LRU: Generator Control Unit (GCU) 2
System Description: 24-21-00
Schematic Diagram: 24-21-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 24-21-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

The Generator Control Unit (GCU) 2 detects between two phases a difference in output current larger than 35 A±5 A.

Possible Causes:

  • AC Power Center (ACPC) (A54)
  • Generator Control Unit (GCU) 2 (A57)
  • Generator Line Contactor (GLC)
  • Variable Frequency Generator (VFG) 2 (G2)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only).

The GCU NVMs can only be downloaded at position #2 or #3.

Quick Links:

Removal of the Variable Frequency Generators (VFG) AMM 24-21-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Variable Frequency Generators (VFG) AMM 24-21-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Generator Control Units (GCU) AMM 24-24-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Generator Control Units (GCU) AMM 24-24-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the AC Power Center (ACPC) AMM 24-51-00-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the AC Power Center (ACPC) AMM 24-51-00-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the AC Power Center (ACPC) L-Series Contactors AMM 24-51-33-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the AC Power Center (ACPC) L-Series Contactors AMM 24-51-33-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the AC Power Center (ACPC) Line Current Transformers AMM 24-51-49-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the AC Power Center (ACPC) Line Current Transformers AMM 24-51-49-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. Check for CAIMS message related to the ACPC short circuit fault. Clear/troubleshoot the message first if existed.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  2. Swap GCU 2 with GCU 3 (physically or using the GCU patch cable).
    NOTE: Use PMAT to monitor the fault on GCU.

    1. If system checks are good, replace GCU 2 and do close out.
    2. If fault remains, continue with next step.

  3. Disconnect T1, T2, T3 and G at VFG 2. Perform continuity check (closed circuit= failure) at the terminal block of VFG 2 as follows:

    From To Result
    G2-T1 Ground
    G2-T2 Ground
    G2-T3 Ground

    1. If there is continuity, go to step 20.
    2. If there is no continuity, continue with next step.

  4. Perform wiring checks (open circuit= failure) between VFG 2 and ACPC as follow:

    From To Result
    G2-T1 ACPC VFG2-T4
    G2-T2 ACPC VFG2-T5
    G2-T3 ACPC VFG2-T6

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  5. Disconnect connector G2P1 on the VFG 2. Perform continuity check (open circuit= failure) on VFG 2 as follow:

    From To Result
    G2P1-F G2P1-D
    G2P1-E G2P1-D
    G2P1-J G2P1-D

    1. If there is no continuity, go to step 20.
    2. If there is continuity, continue with next step.

  6. Perform continuity check (closed circuit= failure) on VFG 2 as follows:

    From To Result
    G2P1-F Ground
    G2P1-E Ground
    G2P1-J Ground
    G2P1-D Ground

    1. If there is continuity, go to step 20.
    2. If there is no continuity, continue with next step.

  7. Disconnect GCU 2 connector A57P2. Perform continuity check (open circuit= failure) between G2P1 and A57P2 as follows:

    From To Result
    G2P1-F A57P2-41
    G2P1-E A57P2-42
    G2P1-J A57P2-50
    G2P1-D A57P2-40

    1. If there is no continuity, repair defective wiring as required and do close out.
    2. If there is continuity, continue with next step.

  8. Perform wiring checks (closed circuit= failure) between G2P1 and ground as follow:

    From To Result
    G2P1-F Ground
    G2P1-E Ground
    G2P1-J Ground

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  9. Disconnect ACPC connector A54P7. Perform continuity check (open circuit= failure) between A57P2 and A54P7 as follows:

    From To Result
    A57P2-49 A54P7-E
    A57P2-57 A54P7-F
    A57P2-63 A54P7-G
    A57P2-62 A54P7-H

    1. If there is no continuity, repair defective wiring as required and do close out.
    2. If there is continuity, continue with next step.

  10. Perform wiring checks (closed circuit= failure) between A57P2 and ground as follow:

    From To Result
    A57P2-49 Ground
    A57P2-57 Ground
    A57P2-63 Ground

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  11. Perform continuity check (open circuit= failure) between VFG 2 and K7 as follows:

    From To Result
    G2-T1 K7-A3
    G2-T2 K7-B3
    G2-T3 K7-C3

    1. If there is no continuity, repair defective wiring as required and do close out.
    2. If there is continuity, continue with next step.

  12. Repair wiring (including inside ACPC) between VFG 2 and K7 as follows:

    From To Result
    G2-T1 K7-A3
    G2-T2 K7-B3
    G2-T3 K7-C3

    1. If fault remains, repair defective wiring as required and do close out.
    2. If system checks are good, continue with next step.
      NOTE: Call Bombardier for decision to repair ACPC wiring or replace ACPC.

  13. Perform wiring checks (closed circuit= failure) between VFG 2 and ground as follow:

    From To Result
    G2-T1 Ground
    G2-T2 Ground
    G2-T3 Ground

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  14. On current transducer 2 (LCTA 2), disconnect connector PL2. Perform continuity check (open circuit= failure) in ACPC between A54P7 and PL2 as follows:

    From To Result
    A54P7-E PL2-1
    A54P7-F PL2-2
    A54P7-G PL2-3
    A54P7-H PL2-4

    1. If there is no continuity, go to step 21.
    2. If there is continuity, continue with next step.

  15. Perform continuity check (open circuit= failure) in ACPC between A54P7 and ground as follows:

    From To Result
    A54P7-E Ground
    A54P7-F Ground
    A54P7-G Ground

    1. If there is continuity, go to step 21.
    2. If there is no continuity, continue with next step.

  16. Perform continuity check (open circuit= failure) at connector within PL2 as follows:

    From To Result
    PL2-1 PL2-4
    PL2-2 PL2-4
    PL2-3 PL2-4

    1. If there is no continuity, go to step 18.
    2. If there is continuity, continue with next step.

  17. Perform continuity check (short circuit= failure) at connector between JL2 and ground as follows:

    From To Result
    JL2-1 Ground
    JL2-2 Ground
    JL2-3 Ground

    1. If there is no continuity, go to step 19.
    2. If there is continuity, continue with next step.

  18. Replace LCTA 2.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  19. Replace GLC 2 (K7).

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  20. Swap VFG 2 with VFG 1.

    1. If system checks are good, replace VFG 2 and do close out.
    2. If fault remains, continue with next step.

  21. Replace ACPC.
  22. Do close out.