Message Overview:
Fault Message:
GEN3 ROTOR DIODE FAILURE
Fault Code:
2423199LPS
Associated CAS:
| Reporting LRU: | Generator Control Units (GCU) 3 |
| System Description: | 24-21-00 |
| Schematic Diagram: | 24-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-21-03 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Continuous monitoring in Generator Control Units (GCU) 3 has detected an open circuit on the rotor diode of Variable Frequency Generator (VFG) 3, consequently resulting in Generator 3 being tripped off-line or not come on-line.
Possible Causes:
- Generator Control Unit (GCU) 3 (A58)
- Variable Frequency Generator (VFG) 3 (G3)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCU 1, GCU 2, GCU 3, GCU 4 and the APU GCU into a different position (for troubleshooting only). You can monitor the GCU faults in CAIMS via the active faults page.
Quick Links:
| Removal of the Variable Frequency Generators (VFG) | AMM 24-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Variable Frequency Generators (VFG) | AMM 24-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap GCU 3 with GCU 4 (physically or using the GCU patch cable). Is the fault still present?
- If YES, continue with next step.
- If NO, replace GCU 3 and do close out.
- Replace VFG 3.
- Do close out.