06/27/19
Message Overview:
Fault Message:
GCU3 PIN PROG/SENSE FAULT
Fault Code:
2423251LPS
Associated CAS:
| Reporting LRU: | Generator Control Unit (GCU) 3 |
| System Description: | 24-21-00 |
| Schematic Diagram: | 24-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-21-03 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Generator Control Unit (GCU) 3 has detected a pin programming/sense fault, consequently resulting in Generator 3 being tripped off-line or not come on-line.
Possible Causes:
- Generator Control Unit (GCU) 3 (A58)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCU 1, GCU 2, GCU 3, GCU 4 and the APU GCU into a different position (for troubleshooting only). You can monitor the GCU faults in CAIMS via the active faults page.
Quick Links:
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Disconnect GCU 3 connector A58P2. Use the table below to make sure that the program pins are wired properly:
APU GCU GCU 1 GCU 2 GCU 3 GCU 4 Prog pin 0 P2-18 to P2-34 (Gnd) Open Open Connected Open Connected Prog pin 1 P2-27 to P2-43 (Gnd) Connected Connected Open Open Connected Prog pin 2 P2-17 to P2-35 (Gnd) Open Connected Connected Connected Open Parity pin P2-26 to P2-44 (Gnd) Open Connected Connected Open Connected - If all checks are good, continue with next step.
- If checks do not match the table, repair defective wiring and do close out.
- Replace the GCU 3.
- Do close out.