Message Overview:
Message Name:
GEN4 [LOW OIL LEVEL]
Message Code:
2424230LPS
Associated CAS:
| Reporting LRU: | Variable Frequency Generator (VFG) 4 |
| System Description: | 24-21-00 |
| Schematic Diagram: | 24-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-21-04 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
Low oil level in Variable Frequency Generator (VFG) 4 is detected by the remote oil level sensing, consequently resulting in Generator 4 tripped off-line or not come on-line.
Possible Causes:
- Variable Frequency Generator (VFG) 4 (G4)
- Generator Oil Level Sensor
- Generator Control Unit (GCU) 4 (A59)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter:
- ForumNewsletter_Volume 17_Issue 18_September_10_2020 - Variable Frequency Generator (VFG) Oil System
Notice To Operators (NTO): None
Flight Operation Notifications Manual (FONM): None
A GCU patch cable (GSE REF # 24X-24-02) can be used to interchange GCU 1, GCU 2, GCU 3, GCU 4 and the APU GCU into a different position (for troubleshooting only). You can monitor the GCU faults in the CAIMS via the fault messages page.
Quick Links:
| Visual Check of the Variable Frequency Generator (VFG) Oil System | AMM 24-12-00-210-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Variable Frequency Generators (VFG) | AMM 24-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Variable Frequency Generators (VFG) | AMM 24-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Quantity Check of the Main Generator Oil Supply | AMM 24-25-00-610-803 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Perform a check of the oil quantity in VFG 4 and service if required as per AMM TASK 24-12-00-210-802 - Visual Check of the Variable Frequency Generator (VFG) Oil System. Is the fault still present?
- If YES, continue with next step.
- If NO, do close out.
- Disconnect GCU 4 connector A59P2 and VFG 4 connector G4P1. Perform a continuity check as follows:
From To Result A59P2-33 Ground A59P2-60 Ground - If there is continuity, repair defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A59P2-33 G4P1-K A59P2-60 G4P1-M - If there is continuity, continue with next step.
- If there is no continuity, repair defective wiring as required and do close out.
- Interchange the GCU 4 with GCU 3. Is the fault still present?
- If YES, continue with next step.
- If NO, replace GCU 4 and do close out.
- Replace VFG 4.
- Do close out.