06/28/19
Message Overview:
Fault Message:
ACPC SSPC PWR CARD8 (A15)/R FWD PMP
Fault Code:
2451327ACP
Associated CAS:
| Reporting LRU: | AC Power Center (ACPC) Solid State Power Converter (SSPC) |
| System Description: | 24-50-00 28-21-00 |
| Schematic Diagram: | 24-51-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-51-01 [ Global Express ] [ G5000 ] [ Global XRS ] 28-21-02 [ Global Express ] [ G5000 ] [ Global XRS ] 28-41-08 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The AC Power Center (ACPC) Solid State Power Converter (SSPC) power card has detected a failure with the initialization of the AC SSPCs, the control logic circuitry and/or the load.
Possible Causes:
- AC Power Center (ACPC) Solid-State Power Controller (SSPC) 8
- Right Fwd AC Boost Pump
- AC Power Center (ACPC) (A54)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
- If the pump is inoperative without CAIMS message and breaker is IN, check wires between FMQGC, throttle quadrant and fuel control panel
- If the breaker is always tripping without CAIMS message, check for a short circuit between the R FWD AC BOOST pump and the SSPC #8
Quick Links:
| Removal of the AC Power Center (ACPC) | AMM 24-51-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) | AMM 24-51-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) Solid-State Power Controller |
AMM 24-51-53-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) Solid-State Power Controller |
AMM 24-51-53-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Boost-Pump Cartridges | AMM 28-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Boost-Pump Cartridges | AMM 28-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap SSPC 8 with SSPC 10 and monitor the R AFT BOOST PUMP.
- If system checks are good, replace SSPC 8 card and do close out.
- If fault remains, continue with next step.
- Disconnect the R FWD AC BOOST pump connector B22P1 and remove the SSPC 8 card. Perform continuity check between the connections that follows:
From To Result SSPC 8 P320-25 B22P1-A SSPC 8 P320-28 B22P1-B SSPC 8 P320-31 B22P1-C - If there is no continuity, repair the defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Perform continuity check between the connections that follows:
From To Result SSPC 8 P320-25 Ground SSPC 8 P320-28 Ground SSPC 8 P320-31 Ground SSPC 8 P320-25 SSPC 8 P320-28 SSPC 8 P320-25 SSPC 8 P320-31 SSPC 8 P320-28 SSPC 8 P320-31 - If there is no continuity, replace R FWD AC BOOST pump and do close out.
- If there is continuity, continue with next step.
- Disconnect connector A54P9 and repeat step 3.
- If there is no continuity, repair aircraft interface wiring as required and do close out.
- If continuity, continue with next step.
- Replace ACPC.
- Do close out.