06/28/19
Message Overview:
Fault Message:
ACPC SSPC PWR CARD11(A24)/R XFR PMP
Fault Code:
2451330ACP
Associated CAS:
| Reporting LRU: | AC Power Center (ACPC) Solid State Power Converter (SSPC) |
| System Description: | 24-50-00 28-22-00 |
| Schematic Diagram: | 24-51-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-51-01 [ Global Express ] [ G5000 ] [ Global XRS ] 28-22-02 [ Global Express ] [ G5000 ] [ Global XRS ] 28-41-08 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The AC Power Center (ACPC) Solid State Power Converter (SSPC) power card has detected a failure with the initialization of the AC SSPCs, the control logic circuitry and/or the load.
Possible Causes:
- AC Power Center (ACPC) Solid−State Power Controller (SSPC) 11
- Right Center Transfer Pump
- AC Power Center (ACPC) (A54)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
- If the pump is inoperative without CAIMS message and breaker is IN, check wires between FMQGC, FUEL CONTROL PANEL and EMS CDU 1 and 2
- If the breaker is always tripping without CAIMS message, check for a short circuit between the RIGHT TRANSFER PUMP and the SSPC #11
Quick Links:
| Removal of the AC Power Center (ACPC) | AMM 24-51-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) | AMM 24-51-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) Solid-State Power Controller |
AMM 24-51-53-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) Solid-State Power Controller |
AMM 24-51-53-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Center Transfer-Pump Canisters | AMM 28-22-13-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Center Transfer-Pump Canisters | AMM 28-22-13-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap SSPC 11 with SSPC 10 and monitor the R AFT BOOST PUMP.
- If system checks are good, replace SSPC 11 card and do close out.
- If fault remains, continue with next step.
- Disconnect the R CENTER TRANSFER-PUMP connector B33P1 and remove the SSPC 11 card. Perform continuity check between the connections that follows:
From To Result SSPC 11 P430-25 B33P1-A SSPC 11 P430-18 B33P1-B SSPC 11 P430-31 B33P1-C - If there is no continuity, repair the defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Perform continuity check between the connections that follows:
From To Result SSPC 11 P430-25 Ground SSPC 11 P430-18 Ground SSPC 11 P430-31 Ground SSPC 11 P430-25 SSPC 11 P430-18 SSPC 11 P430-25 SSPC 11 P430-31 SSPC 11 P430-18 SSPC 11 P430-31 - If there is no continuity, replace R CENTER TRANSFER-PUMP and do close out.
- If there is continuity, continue with next step.
- Disconnect connector A54P1. Repeat step 4.
- If there is no continuity, repair aircraft wiring interface as required and do close out.
- If continuity, continue with next step.
- Replace ACPC.
- Do close out.