Message Overview:
Fault Message:
DCPC FAN FAILED
Fault Code:
2460462DCP
Associated CAS:
| Reporting LRU: | DC Power Center (DCPC) |
| System Description: | 24-60-00 |
| Schematic Diagram: | 24-31-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-31-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
DC Power Center (DCPC) "DC Power Quality Monitor (DCPQM) 2" does not sense rotation of the DCPC Fan.
Possible Causes:
- DC Power Center (DCPC) Fan
- DC Power Center (DCPC) (A63)
- DC Power Quality Monitor (DCPQM) Card 2
- Electrical Module (EM5)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-24-0252 - “ELEC SYS FAULT” and or “ELEC SYS FAIL” - Nuisance CAS Message during Power Up.
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the DC Power Center (DCPC) | AMM 24-61-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) | AMM 24-61-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) DC Power Quality Monitor | AMM 24-61-13-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) DC Power Quality Monitor | AMM 24-61-13-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) Electronic Modules | AMM 24-61-65-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) Electronic Modules | AMM 24-61-65-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Access DCPC to perform visual inspection of cooling fan assy. Ensure DCPC FAN connector P503 is connected properly.
- Select the Battery Master Switch to ON and check status of fan.
- If fan is not rotating, continue with next step.
- If fan is rotating, go to step 8.
- Check for 28 VDC between DCPC FAN connector and ground as follows:
From To Result P503-A Ground - If voltage are good, go to step 5.
- If no 28 Volts, continue with next step.
- Replace EM 5.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Perform wiring checks between DCPC FAN connector and ground as follow:
From To Status Result P503-B Ground closed circuit P503-C Ground open circuit - If wiring check result is same as status in table above, go to step 7.
- If wiring check result is not same as status in table above, continue with next step.
- Replace DCPC.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace DCPC fan.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace DCPQM 2.
- Do close out.