06/28/19
Message Overview:
Fault Message:
CCBP AC BUS3 SHED RLYK1/DCPC RLYK14
Fault Code:
2460484DCP
Associated CAS:
| Reporting LRU: | DC Power Center (DCPC) |
| System Description: | 24-60-00 |
| Schematic Diagram: | 24-52-00 [ Global Express ] [ G5000 ] [ Global XRS ] 24-61-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-52-01 [ Global Express ] [ G5000 ] [ Global XRS ] 24-61-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The DCPC detects a discrepancy between AC BUS 3 shed relay (K1) and its commanded state.
Possible Causes:
- AC BUS 3 Shed Relay (K1)
- Direct Current Power Center (DCPC) (A63)
- DC Power Center (DCPC) Relay (K14)
- DC Power Center (DCPC) Primary Logic Card (PLC) 1
- DC Power Center (DCPC) Primary Logic Card (PLC) 2
- DC Power Center (DCPC) Primary Logic Card (PLC) 3
- DC Power Center (DCPC) Battery/Ram-Air-Turbine (BATT/RAT) Card
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
NOTE: If you notice a TAT HTR 3 FAIL and L-R WINDSHIELD HT FAIL CAS messages, suspect a CCBP K1 stuck in shed position.
Quick Links:
| Removal of the Cockpit Circuit-Breaker Panel (CCBP) H-Series Contactors | AMM 24-52-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Cockpit Circuit-Breaker Panel (CCBP) H-Series Contactors | AMM 24-52-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) | AMM 24-61-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) | AMM 24-61-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) Primary Logic | AMM 24-61-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) Primary Logic | AMM 24-61-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) Battery/Ram-Air-Turbine Interface Unit | AMM 24-61-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) Battery/Ram-Air-Turbine Interface Unit | AMM 24-61-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) J-Series Relay | AMM 24-61-57-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) J-Series Relay | AMM 24-61-57-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Remove power from the aircraft completely. Gain access to the CCBP and disconnect K1-X2 and K1-12.
- Perform a continuity check on contactor K1 as follows:
From To Result K1-11 K1-12 - If there is continuity, replace contactor K1 and do close out.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result K1-11 Ground - If there is no continuity, repair defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Apply External AC power to the aircraft. Perform a 115 VAC voltage check as follows:
From To Result K1-X1 Ground - If there is no 115 VAC, repair defective wiring as required and do close out.
- If there is 115 VAC, continue with next step.
- Gain access to the DCPC logic assembly and remove all 3 PLCs.
- Perform a continuity check as follows:
From To Result K1-12 Ground - If there is no continuity, go to step 9.
- If there is continuity, continue with next step.
- Disconnect DCPC connector P2 and perform a continuity check as follows:
From To Result K1-12 Ground - If there is no continuity, replace the DCPC and do close out.
- If there is continuity, repair defective wiring as required and continue with next step.
- Reconnect DCPC connector P2 and perform a continuity check as follows:
From To Result K1-12 P110B-30 K1-12 P210B-30 K1-12 P310B-30 - If there is no continuity, repair defective wiring as required or replace DCPC if open circuit is located inside the DCPC and do close out.
- If there is continuity, continue with next step.
- Perform a continuity check as follows:
From To Result K1-X2 Ground - If there is no continuity, go to step 13.
- If there is continuity, continue with next step.
- Disconnect DCPC connector P2 and perform a continuity check as follows:
From To Result K1-X2 Ground - If there is continuity, repair defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Disconnect Relay K14-B2. (You may consider disconnecting K14 only one pin at a time as this relay is soldered).
- With DCPC connector P2 still disconnected, perform a continuity check as follows:
From To Result K14-B2 (Aircraft side lead) Ground K14-B2 (Relay side lead) Ground - If there is continuity on the aircraft side, replace the DCPC and do close out.
- If there is continuity on the relay side, replace K14 and do close out.
- If there is no continuity, continue with next step.
- Apply Ground Service power to the aircraft and perform a continuity check to ground as follows (PLCs need to be installed for this test):
From To Result K1-X2 Ground - If there is continuity, make sure the fault message is no longer present and do close out.
- If there is no continuity to ground, continue with next step.
- Gain access to the DCPC Logic assembly and remove all three PLCs.
- Disconnect K14-X1 and K14-X2 and perform a continuity check as follows:
From To Result K14-X2 P110C-15 K14-X2 P210C-15 K14-X2 P310C-15 - If there is continuity, replace the DCPC and do close out.
- If there is no continuity, continue with next step.
- Apply EXT AC power to the aircraft and perform a 28 VDC voltage check as follows:
From To Result K14-X1 Ground - If there is 28 VDC, make sure the fault message is no longer present and do close out
- If there is no 28 VDC, continue with next step.
- Replace the DCPC BATT/RAT Interface card.
- Do close out.