06/28/19
Message Overview:
Fault Message:
RAT GCU FAILED K3 / RATLC FAILED
Fault Code:
2460491DCP
Associated CAS:
| Reporting LRU: | Ram-Air-Turbine Generator Control Unit (RAT GCU) |
| System Description: | 24-50-00 |
| Schematic Diagram: | 24-23-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-23-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Fault message posted when RAT DEPLOY status from Ram-Air-Turbine Generator Control Unit (RAT GCU) and RAT Line Contactor (RATLC) Status are not in the proper configuration during the initiated RAT TEST.
Possible Causes:
- Cockpit Circuit Breaker Panel (CCBP) (A35)
- Ram Air Turbine (RAT) Line Contactor (RATLC) (K3)
- Ram-Air-Turbine Generator Control Unit (RAT GCU) (A191)
- Battery/Ram-Air-Turbine Interface (BAT RAT I/F) Card
- DC Power Center (DCPC) (A63)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Ram-Air-Turbine Generator Control Unit (RAT GCU) | AMM 24-23-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Ram-Air-Turbine Generator Control Unit (RAT GCU) | AMM 24-23-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Cockpit Circuit-Breaker Panel (CCBP)H-Series Contactors | AMM 24-52-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Cockpit Circuit-Breaker Panel (CCBP)H-Series Contactors | AMM 24-52-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) | AMM 24-61-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) | AMM 24-61-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC)Battery/Ram-Air-Turbine Interface Unit | AMM 24-61-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC)Battery/Ram-Air-Turbine Interface Unit | AMM 24-61-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Make sure the RAT is not deployed. Remove power from the A/C. Disconnect DCPC connector A63P2. Perform a continuity check as follows:
From To Result A63P2-J Ground - If there is no continuity, go to step 3.
- If there is continuity, continue with next step.
- Access the CCBP K3. Disconnect RATLC K3 contact 12. Perform a continuity check as follows:
From To Result A63P2-J Ground - If there is no continuity, replace RATLC K3 and do close out.
- If there is continuity, repair defective wiring as required and continue with next step.
- Disconnect RAT GCU connector A191P1. Perform a continuity check as follows:
From To Result A191P1-A Ground A191P1-B Ground - If there is continuity, repair defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result K3-12 A63P2-J A191P1-A A63P2-M A191P1-B A63P2-L - If there is no continuity, repair defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Perform a continuity check on DCPC as follows:
From To Result A63J2-L Ground - If there is no continuity, go to step 12.
- If there is continuity, continue with next step.
- Remove BATT/RAT interface card. Perform a continuity check as follows:
From To Result A63J2-M Ground A63J2-J Ground - If there is continuity, go to step 12.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A63J2-M P410A-8 A63J2-J P410A-11 - If there is no continuity, go to step 12.
- If there is continuity, continue with next step.
- Disconnect RAT GCU connector A191P1. Perform a continuity check as follows:
From To Result A191P1-b Ground A191P1-D Ground - If there is continuity, repair defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A191P1-b K3-X1 A191P1-D K3-X2 - If there is no continuity, repair defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Replace BATT/RAT interface card. Is the fault resolved?
- If YES, do close out.
- If NO, continue with next step.
- Replace RAT GCU.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace DCPC.
- Do close out.