07/01/19
Message Overview:
Fault Message:
EMS CDU1A RX DAU1B ARINC FAULT/WRG
Fault Code:
2470411CDU
Associated CAS:
| Reporting LRU: | Electrical Management System Control Display Unit (EMS CDU) 1 |
| System Description: | 24-70-00 |
| Schematic Diagram: | 24-70-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-70-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Electrical Management System Control-and-Display Unit (EMS CDU) 1 (A91) Channel A has detected a fault with the ARINC input bus from Data Acquisition Unit (DAU) 1 (A18) Channel B.
Possible Causes:
- Electrical Management System Control Display Unit (EMS CDU) 1 (A94)
- Data Acquisition Unit (DAU) 1 (A17)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the DC External-Power Receptacle | AMM 24-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC External-Power Receptacle | AMM 24-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Electrical Management System Control-and-Display Units (EMS CDU) |
AMM 24-70-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Electrical Management System Control-and-Display Units (EMS CDU) |
AMM 24-70-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap DAU 1 with DAU 2. Is the fault still present?
- If YES, continue with next step.
- If NO, replace DAU 1 and do close out.
- Disconnect EMS CDU 1 connector A94P2 and access DAU 1 connector A17CP1. Perform a continuity check as follows:
From To Result A94P2-1 Ground A94P2-2 Ground - If there is continuity, repair defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A94P2-1 A17CP1-K1 A94P2-2 A17CP1-K2 - If there is continuity, continue with next step.
- If there is no continuity, repair defective wiring as required and do close out.
- Replace EMS CDU 1.
- Do close out.