07/20/21
Message Overview:
Message Name:
BOTTLE 2 LOW PRESSURE /WRG
Message Code:
261002EWK
Associated CAS:
| Reporting LRU: | Fire Detection and Extinguishing (FIDEEX) Control Unit |
| System Description: | 26-21-00 |
| Schematic Diagram: | 26-21-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 26-21-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
This message shows when Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit detects a low pressure in the Fire Bottle 2 System.
Possible Causes:
- Fire Extinguisher (FIREX) Container
- Fire Extinguisher (FIREX) Bottle 2 (A112)
- Fire Detection and Extinguishing (FIDEEX) Control Unit (A106)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit | AMM 26-10-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit | AMM 26-10-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Fire Extinguisher Containers | AMM 26-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Fire Extinguisher Containers | AMM 26-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Fire Extinguisher Container | CMM 26-21-65 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10 [ Global Express ] [ G5000 ] [ [ Global XRS ] |
Troubleshooting Recommendations:
- Check the pressure gauge indication on the FIREX bottle.
- If gauge shows an indication of 250 ±25 psi (1724 ±172 Pa) or less, go to step 3.
- If not, continue with next step.
- Disconnect Fire Extinguisher Container connector A112P4 and FIDEEX control unit connector A106P2. Perform a continuity check as follows:
From To Expected Result Result A112P4-3 Ground Open A112P4-2 Ground Open A112P4-3 A106P2-50 Continuity A112P4-2 A106P2-40 Continuity - If wiring defects are found, repair defective associated wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace the Fire Extinguisher Container. Is the fault still present?
- If YES, continue with next step.
- If NO, do close out.
- Replace the FIDEEX control unit.
- Do close out.