Message Overview:
Fault Message:
FLAP RESOLVER EXCITATION/SFCU#2/WRG
Fault Code:
2752257STD
Associated CAS:
| Reporting LRU: | Slat/Flap Control Unit (SFCU) 2 |
| System Description: | 27-52-00 |
| Schematic Diagram: | 27-50-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 27-50-04 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
When one of the following conditions occurs:
- The output voltage is not within the permitted range
- The output current is not within the permitted range
Possible Causes:
- Slat Flap Control Unit (SFCU) 2 (A95)
- Left Flap Resolver (MT67)
- Right Flap Resolver (MT72)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-45-0065 - CAIMS Nuisance Fault Messages
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Flap Resolvers | AMM 27-52-49-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Flap Resolvers | AMM 27-52-49-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- On the EMS CDU, select CTRL function and SLAT/FLAP RESET.
NOTE: Wait at least one minute after SFCU reset to allow self-test to run.- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap SFCU 2 with SFCU 1.
- If system checks are good, replace SFCU 2 and do close out.
- If fault remains, continue with next step.
- Check resistance value as follows:
NOTE: Performing this resistance check will verify the interface wiring in addition to the resolver.Source From To Expected Result Result from Left Flap Resolver A95AP1-96 A95AP1-95 13 to 24 ohms from Right Flap Resolver A95AP1-82 A95AP1-81 13 to 24 ohms - If resistance checks are out of tolerance, repair defective wiring as required and do close out.
- If resistance checks are within tolerance, continue with next step.
- Perform a resistance check of the resolver as follows:
Source From To Expected Result Result Left Flap Resolver MT67J1-8 MT67J1-7 13 to 24 ohms Right Flap Resolver MT72J1-8 MT72J1-7 13 to 24 ohms - If resistance checks are out of tolerance, go to step 6.
- If resistance of the resolver is within tolerance, continue with next step.
- Perform wiring checks between the applicable SFCU and resolver.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace resolver.
- Do close out.