Message Overview:
Fault Message:
RTDEX 3/WRG/DAU 2
Fault Code:
3143037DAU
Associated CAS:
| Reporting LRU: | Data Acquisition Unit (DAU) 2 |
| System Description: | 31-40-00 |
| Schematic Diagram: | 21-52-00 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-52-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Data Acquisition Unit (DAU) 2 senses that the excitation voltage for the Right Pack Discharge Temperature-Sensor is out of range.
Possible Causes:
- Right Pack Discharge Temperature Sensor (E33)
- Data Acquisition Unit (DAU) 2 (A18)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Pack Discharge Temperature-Sensors | AMM 21-52-37-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Pack Discharge Temperature-Sensors | AMM 21-52-37-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Connect Electrical Power to the Aircraft | AMM 24-00-00-861-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Remove the Electrical Power from the Aircraft | AMM 24-00-00-861-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Opening of Non-Thermal Circuit Breakers | AMM 24-00-00-863-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Closing of Non-Thermal Circuit Breakers | AMM 24-00-00-863-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Electrical/Electronic Safety Precautions | AMM 24-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Active Faults | AMM 45-45-00-970-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Stored Faults | AMM 45-45-00-970-803 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Safety Precautions - Maintenance Practices - ALL | SPM 20-00-01-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Disconnect the connector E33P1 from right pack discharge temperature-sensor and remove the DAU 2 to get access to connector A18BP1. Perform a continuity check as follows:
From To Result E33P1-4 A18BP1-D10 E33P1-5 A18BP1-E10 E33P1-SH A18BP1-SH - If there is no continuity, repair or replace defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Perform a continuity check as follows:
From To Result E33P1-4 Ground E33P1-5 Ground - If there is continuity, repair or replace defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Swap initial right pack discharge temperature-sensor with left pack discharge temperature-sensor. Is the fault still present?
- If NO, replace the right pack discharge temperature-sensor and do close out.
- If YES, continue with next step.
- Replace DAU 2.
- Do close out.