Message Overview:
Fault Message:
RVTEXLO 2/WRG/DAU 2
Fault Code:
3143043DAU
Associated CAS:
| Reporting LRU: | Data Acquisition Unit (DAU) 2 |
| System Description: | 31-40-00 |
| Schematic Diagram: | 31-42-00 [ Global Express ] [ G5000 ] [ Global XRS ] 32-51-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 31-42-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Data Acquisition Unit (DAU 2) senses that the excitation for the Right Column Position Transducer on CH B is out of range.
Possible Causes:
- Right Column Position Rotary Variable Differential Transducer (RVDT) (MT217)
- Data Acquisition Unit (DAU) 2 (A18)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Electrical/Electronic Safety Precautions | AMM 24-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Rudder-Control Rotary-Variable Differential-Transducer (RVDT) | AMM 32-51-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Rudder-Control Rotary-Variable Differential-Transducer (RVDT) | AMM 32-51-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Stored Faults | AMM 45-45-00-970-803 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Safety Precautions - Maintenance Practices - ALL | SPM 20-00-01-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Remove the DAU 2 to get access to the connector A18BP1 and right column position transducer to get access to the connector MT217P1. Perform a continuity check as follows:
From To Result A 18BP1-B5 MT217P1-3 A 18BP1-C5 MT217P1-2 - If there is no continuity, repair or replace defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A 18BP1-B5 Ground A 18BP1-C5 Ground - If there is continuity, repair or replace defective wiring as required and do close out.
- If there is no continuity, continue with the next step.
- Swap DAU 2 with DAU 4. Is the fault still present?
- If NO, replace DAU 2 and do close out.
- If YES, continue with next step.
- Replace the right column position transducer.
- Do close out.