Message Overview:
Fault Message:
SFCU_2 INVALID
Fault Code:
3147044DAU
Associated CAS:
| Reporting LRU: | Data Acquisition Unit (DAU) 4 |
| System Description: | 31-40-00 |
| Schematic Diagram: | 27-50-00 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 27-50-02 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-04 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Data Acquisition Unit (DAU) 4 reports that the Line Replaceable Unit (LRU) on label 270 is transmitted from the Slat/Flap Control Unit (SFCU) 2 with incorrect Source Destination Identifier (SDI) or invalid Sign Status Matrix (SSM).
Possible Causes:
- Data Acquisition Unit (DAU) 4 (A31)
- Slat/Flap Control Unit (SFCU) 2 (A95)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Connect Electrical Power to the Aircraft | AMM 24-00-00-861-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Remove the Electrical Power from the Aircraft | AMM 24-00-00-861-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Electrical/Electronic Safety Precautions | AMM 24-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Active Faults | AMM 45-45-00-970-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Stored Faults | AMM 45-45-00-970-803 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Safety Precautions - Maintenance Practices - ALL | SPM 20-00-01-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Remove DAU 4 to get access to the connector A31CP1 and SFCU 2 to get access to the connector A95AP1. Perform a continuity check as follows:
From To Result A31CP1-H8 A95AP1-66 A31CP1-J8 A95AP1-79 - If there is no continuity, repair or replace defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A31CP1-H8 Ground A31CP1-J8 Ground - If there is continuity, repair or replace defective wiring as required and do close out.
- If there is no continuity, continue with next step.
- Swap DAU 4 with DAU 2.
- If system checks are good, replace DAU 4 and do close out.
- If fault remains, continue with next step.
- Replace the SFCU 2.
- Do close out.