08/20/19
Message Overview:
Fault Message:
DEFOG FAULT/EVSHC/WRG
Fault Code:
3000142IN
Associated CAS:
| Reporting LRU: | Enhanced Vision System Heater Controller (EVSHC) |
| System Description: | 34-33-00 |
| Schematic Diagram: | 34-33-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 34-33-03 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Missing or invalid input of defog set point label (ARINC LABEL 204) from the Head-Up Flight Display Computer (HFDC) to the Enhanced Vision System (EVS) Heater Controller when the EVS Infrared Sensor Unit (ISU) is selected on.
Possible Causes:
- Head-Up Flight Display Computer (HUFDC) (A250)
- Data Acquisition Unit (DAU) 2 (A18)
- Data Acquisition Unit (DAU) 4 (A31)
- Enhanced Vision System Heater Controller (EVSHC) (A315)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Head-Up-Display (HUD) Computer | AMM 34-32-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Head-Up-Display (HUD) Computer | AMM 34-32-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Enhanced Vision System (EVS) Heater Controller |
AMM 34-33-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Enhanced Vision System (EVS) Heater Controller |
AMM 34-33-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Using the Bus Reader, read label 165 “ISU Corrected Temp” coming out of the HUD computer. Make sure label 165 is present and valid.
- Using the Bus Reader, read ASCB WSP56, Data Set 2 “Demist Set “Point”, coming out of from DAU4. Make sure WSP 56 Data set 2 is present and valid.
- Using the Bus Reader, read label 204 “Demist Set “Point”, coming out of the DAU 2. Make sure label 204 is present and valid.
- Replace EVSHC.
- Do close out.