08/26/19
Message Overview:
Fault Message:
MADC3/WRG/ COM FAULT
Fault Code:
343000DHUD
Associated CAS:
| Reporting LRU: | Head-Up-Display (HUD) System |
| System Description: | 34-32-00 |
| Schematic Diagram: | 34-32-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 34-11-04 [ Global Express ] [ G5000 ] [ Global XRS ] 34-32-03 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Head-Up-Display (HUD) System does not receive data from the Integrated Avionics Computer Micro Air Data Computer (MADC).
Possible Causes:
- Head-Up Flight Display Computer (HFDC) (A250)
- Micro Air Data Computer (MADC) 3 (A29)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
If more fault reports are sent by a different system about the micro air-data computer, do the fault isolation of the MADC.
Quick Links:
| Removal of the Micro Air-Data Computers | AMM 34-11-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Micro Air-Data Computers | AMM 34-11-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Head-Up-Display (HUD) Computer |
AMM 34-32-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Head-Up-Display (HUD) Computer |
AMM 34-32-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap MADC 3 with MADC 1.
- If system checks are good, replace MADC 3 and do close out.
- If fault remains, continue with next step.
- Perform a wiring check between MADC 3, JB5 and HUDC as follows:
NOTE: When short circuit is detected, remove all interface components and reinstall one at a time to isolate short.From To Result A29P1-63 A250BP1-E6 A29P1-64 A250BP1-F6 A29P1-SH A250BP1-SH GND A250BP1-B5 A29P1-66 A250BP1-E4 A29P1-67 A250BP1-F4 A29P1-SH A250BP1-SH GND A250BP1-F3 - If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace HUDC.
- Do close out.