Message Overview:
Fault Message:
IRS 2 TEMP / COOLING FAULT
Fault Code:
3440013IR
Associated CAS:
| Reporting LRU: | Inertial Reference Unit (IRU) 2 |
| System Description: | 34-45-00 |
| Schematic Diagram: | 34-45-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 34-45-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The internal Inertial Reference Unit (IRU) temperature is higher than the maximum permitted limit (approximately 72 °C).
Possible Causes:
- Inertial Reference System (IRS) 2 Cooling Fan
- Inertial Reference Unit (IRU) 2 (A33)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Inertial Reference System (IRS) Cooling Fans |
AMM 21-54-01-000-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Inertial Reference System (IRS) Cooling Fans |
AMM 21-54-01-400-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Inertial Reference Units (IRU) | AMM 34-45-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Inertial Reference Units (IRU) | AMM 34-45-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Replace IRU 2 cooling fan.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace IRU 2.
- Do close out.