10/24/23
Message Overview:
Fault Message:
L WAIV/L INBOARD WAIT SENSOR
Fault Code:
3615420BMC
Associated CAS:
| Reporting LRU: | Bleed Management Controller (BMC) 1 |
| System Description: | 30-11-00 |
| Schematic Diagram: | 30-11-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 30-11-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
The Left Inboard Wing Anti-Ice Temperature Sensors (WAITS) has detected a temperature >135°C.
Possible Causes:
- Wing Anti-Ice Temperature Sensors (WAITS) 1
- Bleed Management Controller (BMC) 1 (A69)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
NOTE:
- A bad connection in the sensor circuit can cause this condition.
Quick Links:
| Removal of the Anti-Icing Modulating-and-Shutoff Valves | AMM 30-11-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Anti-Icing Modulating-and-Shutoff Valves | AMM 30-11-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Anti-Icing Temperature Sensors | AMM 30-11-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Anti-Icing Temperature Sensors | AMM 30-11-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Bleed Management Controller | AMM 36-11-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Bleed Management Controller | AMM 36-11-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap WAIV 1 with WAIV 2.
- If system checks are good, replace WAIV 1 and do close out.
- If fault remains, continue with next step.
- Measure the left inboard WAITS resistance. Make sure the sensor is within limits as shown in the table and graph below.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Perform wiring checks between BMC1 and left inboard WAITS.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace BMC 1.
- Do close out.