06/18/20
Message Overview:
Fault Message:
[BMC1] L OUTBD WAIT /DAU /WRG
Fault Code:
3615451BMC
Associated CAS:
| Reporting LRU: | Bleed Management Controller (BMC) 1 |
| System Description: | 30-12-00 |
| Schematic Diagram: | 30-11-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 30-11-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
A Left Wing Leading-Edge Outboard Temperature Sensor has been detected invalid.
Possible Causes:
- Left Outboard Wing Anti-Ice Temperature Sensor (WAITS) (E38)
- Bleed Management Controller (BMC) 1 (A69)
- Data Acquisition Unit (DAU) 3 (A30)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Anti-Icing Temperature Sensors | AMM 30-11-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Anti-Icing Temperature Sensors | AMM 30-11-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Bleed Management Controller | AMM 36-11-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Bleed Management Controller | AMM 36-11-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap DAU 3 with DAU 1.
- If system checks are good, replace DAU 3 and do close out.
- If fault remains, continue with next step.
- Swap BMC 1 with BMC 2.
- If system checks are good, replace BMC 1 and do close out.
- If fault remains, continue with next step.
- Perform wiring checks between BMC 1, DAU 3 and left outboard WAITS.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace LEFT OUTBD WING AI TEMP SENSOR.
- Do close out.