Message Overview:
Message Name:
OP CKT-START MOT DC PWR WRG/SEN WRG
Message Code:
4960112APU
Associated CAS:
| Reporting LRU: | Full Authority Digital Engine Controller (FADEC) |
| System Description: | 49-40-00 - Ignition/Starting |
| Schematic Diagram: | [ Global Express ] [ G5000 ] [ Global XRS ] SSM 49-61-00-101 - APU Automatic Control System |
| Wiring Diagram: | [ Global Express ] [ G5000 ] [ Global XRS ] 49-61-00-01 - Sheet 1 Control - 9002-9129 [ Global Express ] [ G5000 ] [ Global XRS ] 49-61-00-01 - Sheet 2 Fadec Interface - 9002-9129 [ Global Express ] [ G5000 ] [ Global XRS ] 49-61-01-1 - Sheet 1 Control - 9159-9249 [ Global Express ] [ G5000 ] [ Global XRS ] 49-61-01-1 - Sheet 1 Control - 9250-9431 [ Global Express ] [ G5000 ] [ Global XRS ] 49-61-01-1 - Sheet 1 Control - 9127-9129 [ Global Express ] [ G5000 ] [ Global XRS ] 49-61-01-1 - Sheet 1 Control - 9130-9249 |
Message Description:
The start relay feedback voltage is less than 1 volt. This shows a possible open in the signal lines to the Full-Authority Digital Engine-Controller (FADEC).
There is a high resistance between the Auxiliary Power Unit (APU) Full-Authority Digital Engine-Controller (FADEC) and the APU Starter. Experience has shown that (assuming the sense circuit wiring is intact) the problem is Starter Brush wear/sticking.
Possible Causes:
- Auxiliary Power Unit (APU) Full-Authority Digital Engine-Controller (FADEC) (A108)
- Auxiliary Power Unit (APU) Starter Motor (B55) (MPE3)
- Auxiliary Power Unit (APU) Starter Contactor Assembly (ASCA) (A48)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Full Throttle Blog/Forum Articles/Infoservice/Newsletter:
- Honeywell SIL APU-137 - Service Information Letter
- Honeywell SIL APU-99 - Electronic Control Unit (ECU) “No Fault Found” Removals
Flight Operation Notifications Manual (FONM): None
Quick Links:
| Removal of the APU Starter-Contactor Assembly | AMM 24-62-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the APU Starter-Contactor Assembly | AMM 24-62-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| APU Safety Precautions | AMM 49-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Engine Branched Wiring-Harness | AMM 49-12-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Engine Branched Wiring-Harness | AMM 49-12-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Starter Motor | AMM 49-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Starter Motor | AMM 49-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Full-Authority Digital Engine-Controller (FADEC) | AMM 49-61-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Full-Authority Digital Engine-Controller (FADEC) | AMM 49-61-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Remove the APU FADEC and disconnect the APU Starter motor. Inspect the pins/sockets/lugs for damage, corrosion and/or push back. Perform a continuity check between APU Starter Motor (-) negative and (+) positive terminals (MPE3) as follows:
From To Result A108BP1-H9 MPE3-NEG A108BP1-G9 MPE3-POS - If there is continuity, go to step 3.
- If there is no continuity, continue with next step.
- Perform a continuity check between the APU connector P1 and the engine branched wiring harness as follows:
From To Result APU P1-5 Negative cable APU P1-4 Positive cable - If there is no continuity, go to step 5.
- If there is continuity, repair defective wiring as required and do close out.
- Perform a continuity check between the APU FADEC and relay K2 inside the ASCA as follows:
From To Result A108BP1-C5 A48P2-C - If there is no continuity, go to step 5.
- If there is continuity, continue with next step.
- Perform continuity check between relay K2 inside the ASCA and the APU Start Motor B55 (MPE3) as follows:
From To Result MPE3-POS A48P2-T5 MPE3-POS Ground - If there is continuity, go to step 6.
- If there is no continuity, continue with next step.
- Replace engine branched wiring-harness. Is the fault still present?
- If NO, do close out.
- If YES, continue with next step.
- Perform a relay check inside the ASCA (A48) on the APU Start Contactor relay K2.
- If relay does not check out, go to step 9.
- If relay checks out, continue with next step.
- Replace APU Starter Motor.
- If APU Start Motor engages, do close out.
- If APU Start Motor still does not engage, continue with next step.
- Replace APU FADEC.
- If starter motor engages, do close out.
- If starter motor will not engage, continue with next step.
- Replace ASCA.
- Do close out.