Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

09/19/19

Message Overview:

Fault Message:

APU GCU [LOAD LEVEL SIG OUT HIGH]

Fault Code:

4960235APU

Associated CAS:

None

Reporting LRU: Full-Authority Digital Engine-Controller (FADEC)
System Description: 49-60-00
Schematic Diagram: 49-61-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 24-22-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]
49-61-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

The Auxiliary Power Unit (APU) Generator load level input conditioning voltage in the Full-Authority Digital Engine-Controller (FADEC) is out of range high.

Possible Causes:

  • Auxiliary Power Unit (APU) Generator Control Unit (GCU) (A109)
  • Full-Authority Digital Engine-Controller (FADEC) (A108)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

Quick Links:

Opening of Non-Thermal Circuit Breakers AMM 24-00-00-863-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Closing of Non-Thermal Circuit Breakers AMM 24-00-00-863-802 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Electrical/Electronic Safety Precautions AMM 24-00-00-910-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Full-Authority Digital
Engine-Controller (FADEC)
AMM 49-61-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Full-Authority Digital
Engine-Controller (FADEC)
AMM 49-61-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Safety Precautions - Maintenance Practices - ALL SPM 20-00-01-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. Check the AC wiring-harness for bare wiring, kinks, worn areas and other damage.

    1. If there is damage, repair defective wiring as required and do close out.
    2. If there is no damage, continue with next step.

  2. Disconnect the connector P619 at the AFT pressure bulkhead (861 LHS) and remove the FADEC (A108). Perform a continuity check as follows:

    From To Result
    P619-79 A108BP1-G10
    P619-80 A108BP1-H10

    1. If there is no continuity, repair defective wiring as required and do close out.
    2. If there is continuity, continue with next step.

  3. Perform a continuity check as follows:

    From To Expected Result Result
    P619-79 Ground > 1 megaohm
    P619-80 Ground > 1 megaohm
    A108BP1-G10 Ground > 1 megaohm
    A108BP1-H10 Ground > 1 megaohm

    1. If resistance value is not more than one megaohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is more than one megaohm for each wire, continue with next step.

  4. Disconnect the P601 connector and perform a continuity check as follows:

    From To Expected Result Result
    P601-A A108BP1-G5 < 1 megaohm

    1. If resistance value is not less than one megaohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is less than one megaohm for each wire, continue with next step.

  5. Perform a continuity check as follows:

    From To Expected Result Result
    P601-A Ground > 1 megaohm
    A108BP1-G5 Ground > 1 megaohm

    1. If resistance value is not more than one megaohm, repair defective wiring as required and do close out.
    2. If resistance value is more than one megaohm, continue with next step.

  6. Disconnect the connector J619 at the AFT pressure bulkhead (861 LHS) and connector P320 (STN 485). Perform a continuity check as follows:

    From To Expected Result Result
    J619-79 P320-118 < 1 megaohm
    J619-80 P320-117 < 1 megaohm

    1. If resistance value is not less than one megaohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is less than one megaohm for each wire, continue with next step.

  7. Perform a continuity check as follows:

    From To Expected Result Result
    J619-79 Ground > 1 megaohm
    J619-80 Ground > 1 megaohm
    P320-118 Ground > 1 megaohm
    P320-117 Ground > 1 megaohm

    1. If resistance value is not more than one megaohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is more than one megaohm for each wire, continue with next step.

  8. Disconnect J601 connector at the AFT pressure bulkhead (861 LHS) and P325 connector (STN 485). Perform a continuity check as follows:

    From To Expected Result Result
    J601-A P325-11 < 1 ohm

    1. If resistance value is not less than one ohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is less than one ohm for each wire, continue with next step.

  9. Disconnect the connector J320 (STN 485) and connector A109P2 from the APU generator (A109). Perform a continuity check as follows:

    From To Expected Result Result
    J320-118 A109P2-64 < 1 ohm
    J320-117 A109P2-66 < 1 ohm

    1. If resistance value is not less than one ohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is less than one ohm for each wire, continue with next step.

  10. Perform a continuity check as follows:

    From To Expected Result Result
    J320-118 Ground > 1 megaohm
    J320-117 Ground > 1 megaohm
    A109P2-64 Ground > 1 megaohm
    A109P2-66 Ground > 1 megaohm

    1. If resistance value is not more than one megaohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is more than one megaohm for each wire, continue with next step.

  11. Disconnect the J325 connector (STN 485) and perform a continuity check as follows:

    From To Expected Result Result
    J325-11 A109P2-53 < 1 ohm

    1. If resistance value is not less than one ohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is less than one ohm for each wire, continue with next step.

  12. Perform a continuity check as follows:

    From To Expected Result Result
    J325-11 Ground > 1 megaohm
    A109P2-53 Ground > 1 megaohm

    1. If resistance value is not more than one megaohm for each wire, repair defective wiring as required and do close out.
    2. If resistance value is more than one megaohm for each wire, continue with next step.

  13. Check if EICAS messages that are related to the APU generator are displayed on the EICAS primary display.

    1. If YES, perform the applicable Troubleshooting for APU generator and do close out.
    2. If NO, continue with next step.

  14. Replace FADEC.
  15. Do close out.