09/23/19
Message Overview:
Fault Message:
OPN CKT-INL DR LIN ACTR/OPN RLY WRG
Fault Code:
4960306APU
Associated CAS:
| Reporting LRU: | Full-Authority Digital Engine-Controller (FADEC) |
| System Description: | 49-60-00 |
| Schematic Diagram: | 49-61-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 49-61-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The signals from the open relay, in the linear actuator, to the Full-Authority Digital Engine-Controller (FADEC) are out of than the expected range. This shows a possible open in the Linear Actuator open-relay or the aircraft wiring harness.
Possible Causes:
- Auxiliary Power Unit (APU) Full-Authority Digital Engine-Controller (FADEC) (A108)
- Door Actuator (A199)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Operational Test of the APU Starter-Contactor Assembly | AMM 24-62-05-710-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Active Faults | AMM 45-45-00-970-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| APU Safety Precautions | AMM 49-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Linear Actuator | AMM 49-14-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Linear Actuator | AMM 49-14-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Full-Authority Digital Engine-Controller (FADEC) | AMM 49-61-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Full-Authority Digital Engine-Controller (FADEC) | AMM 49-61-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Examine the linear actuator (A199) receptacle for contamination and damage.
- If there is contamination or damage, go to step 6.
- If there is no contamination or damage on the receptacle, continue with next step.
- If OPN CKT-INL DR LIN ACTR/OPN RLY WRG still shows on the CAIMS PMAT. Perform a wiring check between aircraft wiring harness (P803) and linear actuator (A199P1).
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- If OPN CKT-INL DR LIN ACTR/OPN RLY WRG still shows on the CAIMS PMAT. Perform a wiring check between aircraft wiring harness (J803) and FADEC (A108BP1).
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- If OPN CKT-INL DR LIN ACTR/OPN RLY WRG still shows on the CAIMS PMAT. Perform a wiring check between aircraft wiring harness (J803) and APU starter-contactor assembly (A48P1).
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- If OPN CKT-INL DR LIN ACTR/OPN RLY WRG still shows on the CAIMS PMAT. Check for 28 Volts minimum on the APU starter-contactor assembly (A48) receptacle A48P1-e.
- If voltage checks are good, do close out.
- If voltage check fails, continue with next step.
- Replace Linear Actuator (A199).
- Do close out.