Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

09/27/19

Message Overview:

Fault Message:

R SAV CH A WRG/SAV [SOL] RNG

Fault Code:

7326116RBR

Associated CAS:

R ENG SAV FAIL
(Caution)

Reporting LRU: Right Engine Electronic Controller (EEC)
System Description: 80 -11-00
Schematic Diagram: 80-11-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 71-50-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

An electrical fault in the Starter Air Valve (SAV) Solenoid circuit CH A has been detected.

Possible Causes:

  • Starter Air Valve (SAV)
  • Right Engine Electronic Controller (EEC)
  • Secondary Power Distribution Assembly (SPDA) 3 (A15)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

  • Both CH A and CH B SAV Solenoid circuits faults must be detected to set the L ENG SAV FAIL (Caution) CAS message

Quick Links:

Removal of the Secondary-Power Distribution Assemblies AMM 24-62-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Secondary-Power Distribution Assemblies AMM 24-62-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Opening of the Cowls AMM 71-10-00-010-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Closing of the Cowls AMM 71-10-00-410-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Eng Electronic Controller (EEC)
Mod 73-101559
EMM 73-21-01-000-801-B00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Eng Electronic Controller (EEC)
Mod 73-101559
EMM 73-21-01-400-801-B001 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Starter Air Valve EMM 80-11-03-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Starter Air Valve EMM 80-11-03-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. Check SAV solenoid channel A for power (P1065-1), 28 VDC should be present when SAV is commanded open.

    1. If there is 28 VDC, go to step 5.
    2. If there is no 28 VDC, continue with next step.

  2. Check for power 28 VDC at right engine disconnect 2JA2-32.

    1. If there is 28 VDC, go to step 4.
    2. If there is no 28 VDC, continue with next step.

  3. Perform wiring checks on the interface wiring between SPDA 3 and the Right Engine disconnect as follow:

    From To Result
    A15P1-N 2JA2-32

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  4. Swap SPDA 3 with SPDA 1. Is the fault still present?

    1. If NO, replace SPDA 3 and do close out.
    2. If YES, investigate the power input to SPDA 3 and continue with next step.

  5. Perform a continuity check for SAV solenoid winding at P1065 as follows:

    From To Result
    P1065-1 P1065-5

    1. If there is no continuity, replace defective SAV and do close out.
    2. If there is continuity, continue with next step.

  6. Perform wiring checks between the SAV and the EEC.

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  7. Perform wiring checks between the engine pylon disconnect 2PA2 and the EEC.

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  8. Swap SAV between engines. Is the fault still present?

    1. If NO, replace defective SAV and do close out.
    2. If YES, continue with next step.

  9. Replace Right EEC.
  10. Do close out.