Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

02/06/20

Message Overview:

Fault Message:

L CH A TURB O'HEAT WRG/PROBE RNG MA

Fault Code:

7327627LBR

Associated CAS:

L FADEC FAULT
(Advisory)

Reporting LRU: Left Engine Electronic Controller (EEC)
System Description: 77-20-00
Schematic Diagram: 77-20-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 71-50-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]
77-20-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

There is an open or short circuit in the interface wiring or the Turbine Overheat-Detection Thermocouple. During Engine operation the Turbine Overheat-Detection Circuits are continuously monitored by the Full-Authority Digital Engine-Controller (FADEC).

Possible Causes:

  • Turbine Overheat-Detection Thermocouple
  • Left Engine Electronic Controller (EEC)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

Quick Links:

Connect Electrical Power to the Aircraft AMM 24-00-00-861-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Remove the Electrical Power from the Aircraft AMM 24-00-00-861-802 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Opening of Non-Thermal Circuit Breakers AMM 24-00-00-863-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Closing of Non-Thermal Circuit Breakers AMM 24-00-00-863-802 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Electrical/Electronic Safety Precautions AMM 24-00-00-910-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
CAIMS PMAT General Instructions AMM 45-45-00-970-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Access to Active Faults AMM 45-45-00-970-802 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Access to Stored Faults AMM 45-45-00-970-803 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Engine Safety Precautions AMM 71-00-00-910-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Start the Engine AMM 71-00-00-866-806 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Engine Shutdown (Usual) AMM 71-00-00-866-809 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Opening of the Cowls AMM 71-10-00-010-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Closing of the Cowls AMM 71-10-00-410-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Bypass-Duct Access Panels (451AL/461AL,
451BL/461BL, 451CL/461CL, 451DL/461DL,
451EL/461EL, 452FR/462FR, 452GR/462GR,
452HR/462HR, 452JR/462JR, 452KR/462KR)
AMM 72-71-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Bypass-Duct Access Panels (451AL/461AL,
451BL/461BL, 451CL/461CL, 451DL/461DL,
451EL/461EL, 452FR/462FR, 452GR/462GR,
452HR/462HR, 452JR/462JR, 452KR/462KR)
AMM 72-71-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Deactivation of the Thrust Reverser (for Maintenance) AMM 78-30-00-040-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Activation of the Thrust Reverser (for Maintenance) AMM 78-30-00-440-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Connection of Electrical Connectors EMM 70-50-01-910-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Combustion Section Fairings EMM 72-03-02-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Combustion Section Fairings EMM 72-03-02-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Turbine Overheat-Detection Thermocouple EMM 77-23-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Turbine Overheat-Detection Thermocouple EMM 77-23-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Safety Precautions - Maintenance Practices - ALL SPM 20-00-01-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. Perform a visual inspection of the turbine overheat-detection system. Inspect for damage and proper installation.
    NOTE: Look specially for signs of damage adjacent to clip locations.

    1. If damage or defect is found, rectify or repair as required and do close out.
    2. If damage or defect is not found, continue with next step.

  2. Disconnect the EEC connector (P1044) and the bypass duct connectors (P1030 and J1030). Disconnect the interface wiring at the terminal blocks TB2114 and TB2115 and at the ground connector (GC2106). Perform a visual inspection of the associated wiring and connectors for damage between the connectors and the terminal blocks.
    NOTE: Look specially for signs of chafing adjacent to clip locations, condition of connector pins and wiring kink or strain.

    1. If defects are found, rectify or repair as required and do close out.
    2. If defects are not found, continue with next step.

  3. Perform a continuity check between the terminal blocks TB2114 and TB2115 (Chromel and Alumel terminal lugs) and the connector P1030 as follows:

    From To Result
    TB2114 P1030-30
    TB2115 P1030-31

    1. If there is no continuity, repair defective wiring as required and do close out.
    2. If there is continuity, continue with next step.

  4. Perform a continuity check between the connectors J1030 and P1044 as follows:

    From To Result
    J1030-30 P1044-52
    J1030-31 P1044-31

    1. If there is no continuity, repair defective wiring as required and do close out.
    2. If there is continuity, continue with next step.

  5. Perform a insulation resistance check of the wiring between the bypass duct and the terminal blocks as follows:

    From To Resistance Value Result
    P1030-30 Ground 20 MΩ or more
    P1030-31 Ground 20 MΩ or more

    1. If the resistance value is less than the value specified in the table or if there is a short to ground, repair defective wiring as required and do close out.
    2. If there is no continuity or resistance value is as specified in the table, continue with next step.

  6. Perform a insulation resistance check of the wiring between the EEC and the bypass duct connector (P1044) as follows:

    From To Resistance Value Result
    P1044-52 Ground 20 MΩ or more
    P1044-31 Ground 20 MΩ or more

    1. If the resistance value is less than the value specified in the table or if there is a short to ground, repair defective wiring as required and do close out.
    2. If there is no continuity or resistance value is as specified in the table, continue with next step.

  7. Replace turbine overheat-detection thermocouple. Is the fault still present?

    1. If YES, continue with next step.
    2. If NO, do close out.

  8. Swap both EECs to confirm faulty unit and replace if required.
  9. Do close out.