Message Overview:
Message Name:
ACPC CONTACTOR TACK WELDING
| Message Code: | 240OBS002 |
| Effectivity: | All |
| System: | AC Power Center (ACPC) |
| System Description: | 24-21-00 |
| Schematic Diagram: | None |
| Wiring Diagram: | 24-51-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
AC Power Center (ACPC) detects Contactor at fault.
Possible Causes:
- AC Power Center (ACPC) (A54)
- Generator Control Unit (GCU) 1 (A56)
- Generator Control Unit (GCU) 2 (A57)
- Generator Control Unit (GCU) 3 (A58)
- Generator Control Unit (GCU) 4 (A59)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter:
- Forum_vol8_issue06_mar-22-11 - ACPC Contactor
Quick Links:
| Removal of the APU Generator | AMM 24-22-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the APU Generator | AMM 24-22-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) | AMM 24-51-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) | AMM 24-51-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) L-Series Contactors |
AMM 24-51-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) L-Series Contactors |
AMM 24-51-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Functional Test of the AC Power Center (ACPC) L-Series Contactors K2, K3 and K5 |
AMM 24-51-33-720-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) LC-Series Contactors (K4, K6, K9, K12) |
AMM 24-51-37-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) LC-Series Contactors (K4, K6, K9, K12) |
AMM 24-51-37-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Functional Test of the AC Power Center (ACPC) LC-Series Contactors (K4, K6, K9, K12) |
AMM 24-51-37-720-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
NOTE: During any generator switching, all the ACMPs (hydraulic pumps) should be turned off.
- When CAS messages, CAIMS, synoptic page, or NVM download error code analysis, indicate that contactor P/N 5911740-1, at contactor positions K4, K6, K9, K12, or P/N 5911739-1 at contactor positions K2, K3, K5, K7, K8, K10, K11, K13, may be at fault, it is possible to restore these contactors full functionally by performing the generator switching sequence.
- Power down and up the aircraft.
- Ensure that both engines are running, the BMS (Bleed Management System) is on and all ACMPs are off (including AC pump 3A).
- If one or more conditions are not satisfied, apply condition as required and continue with next step.
- If all conditions are satisfied, continue with next step.
- Check for CAS messages, CAIMS, synoptic page, or NVM download error code analysis, indicate that contactor P/N 5911740-1, at contactor positions K4, K6, K9, K12, or P/N 5911739-1 at contactor positions K2, K3, K5, K7, K8, K10, K11, K13.
- If contactor K6 or K10 has fault, go to step 9.
- If contactor K9 or K7 has fault, go to step 13.
- If contactor K12 or K5 has fault, go to step 17.
- If contactor K11 or K2 has fault, go to step 21.
- If contactor K3 or K8 has fault, go to step 25.
- If contactor K4 or K13 has fault, continue with next step.
- For contactor K4 or K13 fault, on the ELECTRICAL Control Panel set the GEN 2 and GEN 3 PBAs to "ON".
- Verify that AC Electrical Synoptic page shows all the AC busses powered, that the AC Bus 1 is powered from GEN 3 and AC Bus 4 from GEN 2.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Set the GEN 4 PBA on and again verify that all the AC busses are shown as green with the AC Bus 1 and AC Bus 4 being powered this time from GEN 4.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Repeat the GEN 4 on and off switching two or three times to ensure that the AC Bus 1 and AC Bus 4 power source switching follows.
- If there is CAS Message, troubleshoot them first and do close out.
- If there is no CAS Message, continue with next step.
- For contactor K6 or K10 fault, on the ELECTRICAL Control Panel set the GEN 1 and GEN 4 PBAs to "ON".
- Verify that AC Electrical Synoptic page shows all the AC busses powered, that the AC Bus 2 is powered from GEN 4 and AC Bus 3 from GEN 1.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Set the GEN 3 PBA on and again verify that all the AC busses are shown as green with the AC Bus 2 and AC Bus 3 being powered this time from GEN 3.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Repeat the GEN 3 on and off switching two or three times to ensure that the AC Bus 2 and AC Bus 3 power source switching follows.
- If there is CAS Message, troubleshoot them first and do close out.
- If there is no CAS Message, continue with next step.
- For contactor K9 or K7 fault, on the ELECTRICAL Control Panel set the GEN 1 and GEN 4 PBAs to "ON".
- Verify that AC Electrical Synoptic page shows all the AC busses powered, that the AC Bus 3 is powered from GEN 1 and AC Bus 2 from GEN 4.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Set the GEN 2 PBA on and again verify that all the AC busses are shown as green with the AC Bus 3 and AC Bus 2 being powered this time from GEN 2.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Repeat the GEN 2 on and off switching two or three times to ensure that the AC Bus 3 and AC Bus 2 power source switching follows.
- If there is CAS Message, troubleshoot them first and do close out.
- If there is no CAS Message, continue with next step.
- For contactor K12 or K5 fault, on the ELECTRICAL Control Panel set the GEN 2 and GEN 3 PBAs to "ON".
- Verify that AC Electrical Synoptic page shows all the AC busses powered, that the AC Bus 4 is powered from GEN 2 and AC Bus 1 from GEN 3.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Set the GEN 1 PBA on and again verify that all the AC busses are shown as green with the AC Bus 4 and AC Bus 1 being powered this time from GEN 1.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Repeat the GEN 1 on and off switching two or three times to ensure that the AC Bus 4 and AC Bus 1 power source switching follows.
- If there is CAS Message, troubleshoot them first and do close out.
- If there is no CAS Message, continue with next step.
- For contactor K11 or K2 fault, on the ELECTRICAL control panel set the GEN 3 and APU GEN PBAs to "ON".
- With APU GEN on, turn the GEN 3 on and off switching two or three times to ensure that the AC Bus 4 power source switching follows from GEN 3 to APU GEN and vice versa (K11 switching).
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- With GEN 3 on, turn the APU GEN on and off switching two or three times to ensure that the AC Bus 1 power source switching follows from APU to GEN 3 and vice versa (K2 switching).
NOTE: 'AC BUS 2 & 3 FAIL' and 'DC BUS 2 FAIL' CAS messages will appear with this switching condition.- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Check for CAS message 'AC BUS 2 & 3 FAIL' and 'DC BUS 2 FAIL' appear with this switching condition.
- If there is CAS Message, troubleshoot them first and do close out.
- If there is no CAS Message, continue with next step.
- For contactor K3 or K8 fault, on the Electrical control panel set the GEN 2 and APU GEN PBAs to "ON".
NOTE: only Engine 1 has to be running for this test. - With APU GEN on, turn the GEN 2 on and off switching two or three times to ensure that the AC Bus 1 power source switching follows from GEN 2 to APU GEN and vice versa (K3 switching).
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- With GEN 2 on, turn the APU GEN on and off switching two or three times to ensure that the AC Bus 4 power source switching follows from APU to GEN 2 and vice versa (K8 switching).
NOTE: 'AC BUS 2 & 3 FAIL' and 'DC BUS 2 FAIL' CAS messages will appear with this switching condition.- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Check for CAS message 'AC BUS 2 & 3 FAIL', 'DC BUS 2 FAIL' and 'ELEC SYS' appear with this switching condition.
- If there is no CAS Message, do close out.
- If there is CAS Message, continue with next step.
- Troubleshoot the CAS Message as required.
- Do close out.