Message Overview:
Message Description:
Auxiliary Generator Power-Module (PCB10) has failed.
Possible Causes:
- Generator Control Unit (GCU) Printed Circuit Board 9 (PCB9)
- Auxiliary Generator Power-Module (AGPM) (PCB10)
- APU Generator (G3)
- Auxiliary Power Center (Aux DCPC) (A196)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-24-0023 - Nuisance "ELECTRICAL FAULT" CAS Message During APU Start
- AW300-24-0024 - Electrical System - Troubleshooting Tips
- AW300-24-0137 - Y06 Electrical System Upgrade
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Main Generator | AMM 24-31-05-000-801 |
| Installation of the Main Generator | AMM 24-31-05-400-801 |
| Removal of the APU Generator | AMM 24-31-09-000-801 |
| Installation of the APU Generator | AMM 24-31-09-400-801 |
| Removal of the Generator Power Module (GPM) | AMM 24-31-21-000-801 |
| Installation of the Generator Power Module (GPM) | AMM 24-31-21-400-801 |
| Removal of the Auxiliary Generator Power-Module (AUX GPM) | AMM 24-31-25-000-801 |
| Installation of the Auxiliary Generator Power-Module (AUX GPM) | AMM 24-31-25-400-801 |
| Removal of the Auxiliary DC Power Center (Aux DCPC) | AMM 24-64-01-000-801 |
| Installation of the Auxiliary DC Power Center (Aux DCPC) | AMM 24-64-01-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Swap the GCU PCB9 with either of the engine GCU PCB9. Is the fault message still present?
- If YES, continue with next step.
- If NO, replace the defective GCU PCB9.
- Swap the Auxiliary Generator Power-Module PCB10 with the Right Generator Power Module PCB8 or the Left Generator Power Module PCB7. Is the fault message still present?
- If YES, continue with next step.
- If NO, replace the defective Generator Power-Module.
- Do wiring check of the following wires:
From To Results APU GEN conn. G3P1 - pin L AUX DCPC conn. A196P1 - pin JJ APU GEN conn. G3P1 - pin M AUX DCPC conn. A196P1 - pin z APU GEN conn. G3P1 - pin H AUX DCPC conn. A196P1 - pin D APU GEN conn. G3P1 - pin J AUX DCPC conn. A196P1 - pin d APU GEN conn. G3P1 - pin K AUX DCPC conn. A196P1 - pin E - If wiring check is satisfactory, continue with next step.
- If wiring check is not satisfactory, repair the defective wire.
- Swap the APU Generator (G3) with one of the Main Generator (G1 or G2). Is the fault message still present?
- If YES, continue with next step.
- If NO, replace the defective Generator.
- Replace the AUX DCPC (A196).
- Do close out.