Message Overview:
Fault Message:
[ACSC1-A] FWD DUCT TEMP SENS /WRG
Fault Code:
2161428ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 1 |
| System Description: | 21-60-00 |
| Schematic Diagram: | 21-60-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-51-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Fwd Cabin Duct Temperature Sensor has been detected out of range by Air Conditioning System Controller (ACSC) 1 Channel A.
Possible Causes:
- Duct Temperature Sensor 2 (E22)
- Air Conditioning System Controller (ACSC) 1 (A87)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 -"PACK FAULT" CAS message while CAIMS / OMS is active (Global Express / XRS - 9002 to 9312, 9314 to 9380, 9384 to 9429 and Global 5000 - 9127 to 9383, 9389 to 9400, 9404 to 9431 and 9998)
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Duct Temperature Sensors | AMM 21-60-17-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Duct Temperature Sensors | AMM 21-60-17-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to System Diagnostics | AMM 45-45-00-970-804 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Access System Diagnostics and verify sensor data is valid and compare with other sensor.
- If data is valid, go to step 3.
- If data is not valid, continue with next step.
- Swap Duct Temperature Sensor 2 with Duct Temperature Sensor 1.
- If system checks are good, replace Duct Temperature Sensor 2 and do close out.
- If fault remains, continue with next step.
- Perform a wiring checks between Duct Temperature Sensor 2 and ACSC 1.
- If the wiring checks are not good, repair the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Replace ACSC 1.
- Do close out.