06/12/19
Message Overview:
Fault Message:
[ACSC2-A] RH RECIRCUL FAN /WRG
Fault Code:
2163528ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 2 |
| System Description: | 21-60-00 |
| Schematic Diagram: | 21-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-21-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Right Recirculation Fan has been detected failed by the Right Air Conditioning Controller (ACSC).
Possible Causes:
- Air Conditioning System Controller (ACSC) 2 (A88)
- AC Power Center (ACPC) (A54)
- Recirculation Fan and Check Valve 2 (B21)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 - "PACK FAULT" CAS message while CAIMS / OMS is active (Global Express / XRS - 9002 to 9312, 9314 to 9380, 9384 to 9429 and Global 5000 - 9127 to 9383, 9389 to 9400, 9404 to 9431 and 9998)
Forum Articles/Infoservice/Newsletter: None
CAIMS has Pack Temp. Sensor Data for ACSC controllers on all 4 channels. This will show sensor data and give you an idea of problem areas, even with the air system not operating, but power is on.
Quick Links:
| Removal of the Recirculation Fan and Check Valves | AMM 21-21-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Recirculation Fan and Check Valves | AMM 21-21-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Make sure the recirculation fan is not obstructed.
- Perform wiring checks between ACSC 2 and Right Recirculation Fan.
- If wiring checks are not good, repair defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Perform wiring checks between Right Recirculation Fan and ACPC.
- If wiring checks are not good, repair defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Swap Recirculation Fan 2 with Recirculation Fan 1.
- If the system checks are good, replace Recirculation Fan 2 and do close out.
- If the fault remains, continue with next step.
- Replace ACSC 2.
- Do close out.