06/12/19
Message Overview:
Fault Message:
HUMIDIFIER DRAIN VALVE (HDV)/ WRG
Fault Code:
2163615ECS
Associated CAS:
| Reporting LRU: | Humidifier Control Unit (HCU) |
| System Description: | 21-71-00 |
| Schematic Diagram: | 21-71-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-71-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Humidifier Control Unit (HCU) sense the Humidifier Drain Valve (HDV) is failed closed (humidifier boiler purge time >100 seconds).
Possible Causes:
- Humidifier Control Unit (HCU) (A248)
- Humidifier Drain Valve (HDV) (L53)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter:
Quick Links:
| Functional Test of the Humidifier System | AMM 21-71-00-720-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Drain Valve | AMM 21-71-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Drain Valve | AMM 21-71-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Humidifier Control Unit | AMM 21-71-17-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Humidifier Control Unit | AMM 21-71-17-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Perform wiring checks between HCU and Humidifier Drain Valve (HDV) including HDV grounds.
- If wiring checks are not good, repair the defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Using ATP mode, Send a command to open the HDV. Make sure 28 VDC is present at the HDV connector (Refer to the Functional Test of the Humidifier System (TASK 21−71−00−720−801) to access ATP mode and command HDV to the open position).
- Check for any blockage on the drain line and drain mast.
- Make sure the Drain Mast Heater is serviceable.
- Replace HDV.
- If the system check is good, do close out.
- If the fault remains, continue with next step.
- Replace HCU.
- Do close out.
NOTE: Perform Functional Test of the Humidifier System to confirm the system integrity. This task is the approved Return to Service (RTS) Test for the Humidifier System.
If the operator which to operate the humidifier on the ground as it operates in flight, then use the following attached procedure. Please note that the attached procedure is not approved for RTS and can only be used for troubleshooting purpose. Please note that the 3.5 hours delay can not be bypassed in this procedure.
Humidifier Operation with Aircraft W off W (3.5 hours delay activation).