Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

06/12/19

Message Overview:

Fault Message:

HUMID BOILER OUTLET TEMP SENS /WRG

Fault Code:

2163620ECS

Associated CAS:

HUMIDIFIER FAIL
(Advisory)

Reporting LRU: Humidifier Control Unit (HCU)
System Description: 21-71-00
Schematic Diagram: 21-71-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 21-71-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

The Humidifier Water Boiler Temperature Sensor (HWBTS) has been detected out of range by the Humidifier Control Unit (HCU).

Possible Causes:

  • Humidifier Water Boiler Temperature Sensor (HWBTS) (MT213)
  • Humidifier Control Unit (HCU) (A248)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

Quick Links:

Functional Test of the Humidifier System AMM 21-71-00-720-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Humidifier Control Unit AMM 21-71-17-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Humidifier Control Unit AMM 21-71-17-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Boiler Temperature Sensor AMM 21-71-25-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Boiler Temperature Sensor AMM 21-71-25-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. Perform a wiring check between HCU and HWBTS.

    1. If wiring checks are not good, repair the defective associated wiring and do close out.
    2. If wiring checks are good, continue with next step.

  2. Measure the HWBTS resistance. The resistance should be as per the table below:

    Temperature (°C) Resistance (ohms)

    Temperature (°C) Resistance (ohms)
    -65 148.40000 160 322.01288
    -60 152.42266 170 329.42961
    -50 160.44000 180 336.82204
    -40 168.42103 190 344.19020
    -30 176.36679 200 351.53413
    -20 184.27815 210 358.85385
    -10 192.15575 220 366.14938
    200.0000 230 373.42075
    10 207.81294 240 380.66796
    20 215.60054 250 387.89103
    30 223.36292 260 395.08998
    40 231.10014 270 402.26480
    50 238.81231 280 409.41550
    60 246.49950 290 416.54209
    70 320.0000 300 423.64455
    80 261.79926 310 430.72289
    90 269.41198 320 437.77709
    100 277.0000 330 444.80715
    110 284.56340 340 451.81305
    120 292.10222 350 458.79477
    130 299.61654 360 465.75230
    140 307.10639 370 472.68561
    150 314.57182

    380

    479.59468

    1. If fault indication is gone, do close out.
    2. If fault remains, continue with next step.

  3. Replace HWBTS.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  4. Replace HCU.
  5. Do close out.

NOTE: Perform Functional Test of the Humidifier System to confirm the system integrity. This task is the approved Return to Service (RTS) Test for the Humidifier System.

If the operator which to operate the humidifier on the ground as it operates in flight, then use the following attached procedure. Please note that the attached procedure is not approved for RTS and can only be used for troubleshooting purpose. Please note that the 3.5 hours delay can not be bypassed in this procedure.