Message Overview:
Fault Message:
[ACSC2-B] RH RECIRCUL FAN /WRG
Fault Code:
2164528ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 2 |
| System Description: | 21-20-00 |
| Schematic Diagram: | 21-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-21-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The right Recirculation Fan has been detected failed by the right Air Conditioning System Controller (ACSC).
Possible Causes:
- Air Conditioning System Controller (ACSC) 2 (A88)
- Recirculation Fan And Check Valve 2 (B21)
- AC Power Center (ACPC) (A54)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Recirculation Fan and Check Valves | AMM 21-21-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Recirculation Fan and Check Valves | AMM 21-21-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) | AMM 24-51-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) | AMM 24-51-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Make sure the recirculation fan is not obstructed.
- Swap Recirculation Fan 2 with Recirculation Fan 1.
- If system checks are good, replace Recirculation Fan 2 and do close out.
- If fault remains, continue with next step.
- Swap ACSC 2 with ACSC 1.
- If system checks are good, replace ACSC 2 and do close out.
- If fault remains, continue with next step.
- Perform a wiring check between ACSC 2 and Right Recirculation Fan.
- If the wiring checks are not good, repair the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Perform a wiring check between Right Recirculation Fan and ACPC.
- If the wiring checks are not good, repair the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Replace ACPC.
- Do close out.