Message Overview:
Fault Message:
APUGCU PIN PROGRAMMING FAULT
Fault Code:
2420128LPS
Associated CAS:
| Reporting LRU: | Auxiliary Power Unit (APU) Generator Control Unit (GCU) |
| System Description: | 24-21-00 |
| Schematic Diagram: | 24-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-24-05 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Auxiliary Power Unit (APU) Generator Control Unit (GCU), during initial power up (cold start), has detected a fault in the pin programming wiring or in the pin programming sensing circuit, consequently the Generator will not come on line.
Possible Causes:
- Auxiliary Power Unit (APU) Generator Control Unit (GCU) (A109)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only).
The GCU NVMs can only be downloaded at position #2 or #3.
Quick Links:
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap APU GCU with GCU #2 (physically or using the GCU patch cable).
NOTE: Use PMAT to monitor the fault on GCU.- If system checks are good, replace APU GCU and do close out.
- If fault remains, continue with next step.
- Disconnect connector APU GCU (A109P2).
- Perform wiring checks for open circuits as follow:
From To Result A109P2-27 A109P2-43 - If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Perform wiring checks for short circuits as follow:
From To Result A109P2-17 A109P2-35 A109P2-18 A109P2-34 A109P2-26 A109P2-44 - If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Do close out.