06/20/19
Message Overview:
Fault Message:
APUGCU [DIFF PROTECTION SENSE]
Fault Code:
2420195LPS
Associated CAS:
| Reporting LRU: | Auxiliary Power Unit Generator Control Unit (APU GCU) |
| System Description: | 24-22-00 |
| Schematic Diagram: | 24-22-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-24-05 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Auxiliary Power Unit Generator Control Unit (APU GCU) has detected an internal failure related to its differential current protection sense circuit, consequently resulting in an Auxiliary Power Unit (APU) Generator tripped off-line.
Possible Causes:
- Auxiliary Power Unit Generator Control Unit (APU GCU) (A109)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only).
The GCU NVMs can only be downloaded at position #2 or #3.
Quick Links:
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Replace APU GCU.
NOTE: Use PMAT to monitor the fault on GCU. - Do close out.