Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

06/27/19

Message Overview:

Fault Message:

GCU3 SENSE/GEN3 CONT SW FAULT

Fault Code:

2423254LPS

Associated CAS:

GEN 3 FAIL
(Advisory)

Reporting LRU: Generator Control Unit (GCU) 3
System Description: 24-21-00
Schematic Diagram: 24-21-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 24-21-03 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

Generator Control Unit (GCU) 3 has detected a fault in the Generator Control Switch (GCS)/wiring or in its internal GCS sensing circuit.

GCU GCS sensing circuit has detected the OFF signal as being the same as the ON signal.

Possible Causes:

  • Generator Control Unit (GCU) 3 (A58)
  • Electrical Control Panel (Overhead Panel) (AP3)
  • Generator Control Switch (GCS)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only).

The GCU NVMs can only be downloaded at position #2 or #3.

Quick Links:

Removal of the Generator Control Units (GCU) AMM 24-24-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Generator Control Units (GCU) AMM 24-24-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the ELECTRICAL Control Panel AMM 24-24-05-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the ELECTRICAL Control Panel AMM 24-24-05-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. Swap GCU 3 with GCU 2.

    1. If system checks are good, replace GCU 3 and do close out.
    2. If fault remains, continue with next step.

  2. On GCU #3, disconnect connector A58P2. On the overhead control panel, disconnect connector AP3P2. Perform open circuit checks between GCU 3 and Electrical Control Panel as follow:

    From To Expected Result Result
    A58P2-21 AP3P2-S Open
    A58P2-28 AP3P2-T Open

    1. If an open circuit is detected, repair or replace defective wiring as required and do close out.
    2. If an open circuit is not detected, continue with next step.

  3. On connector A58P2, perform short circuit checks between GCU 3 and ground as follow:

    From To Expected Result Result
    A58P2-21 Ground Short
    A58P2-28 Ground Short

    1. If a short circuit is detected, repair or replace defective wiring as required and do close out.
    2. If a short circuit is not detected, continue with next step.

  4. Perform a continuity check between Electrical Control Panel and ground as follows:

    From To Result
    AP3P2-R GC160

    1. If an open circuit is detected, repair or replace the defective wiring as required and continue with next step.
    2. If a short circuit is detected, go to step 6.

  5. Check the integrity of ground stud GC160.

    1. If defective, repair or replace the ground stud and do close out.
    2. If it is not defective, do close out.

  6. Inspect the electrical control panel internal wiring and the generator control switch (GCS-SDS5).

    1. If a defect is found with the wiring, repair or replace the defective wiring as required and do close out.
    2. If a defect is found on the GCS, continue with next step.

  7. Replace the GCS.
  8. Do close out.