06/28/19
Message Overview:
Fault Message:
DCPC PWR QUALITY MONITOR 1-A7 FAIL
Fault Code:
2460407DCP
Associated CAS:
| Reporting LRU: | DC Power Center (DCPC) |
| System Description: | 24-60-00 |
| Schematic Diagram: | 24-61-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-61-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The DC Power Center (DCPC) Power Quality Monitor Card (DCPQM) has failed the Power Up Built-In Test (PBIT) or Continuous Built-In Test (CBIT).
Possible Causes:
- DC Power Center Power Quality Monitor Card (DCPQM) (p/o A63)
- Battery/Ram-Air Turbine Interface (BATT/RAT I/F) Card (p/o A20)
- DC Power Center (DCPC) (A63)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the DC Power Center (DCPC) | AMM 24-61-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) | AMM 24-61-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) DC Power Quality Monitor | AMM 24-61-13-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) DC Power Quality Monitor | AMM 24-61-13-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) Battery/Ram-Air-Turbine Interface Unit | AMM 24-61-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) Battery/Ram-Air-Turbine Interface Unit | AMM 24-61-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Access the DCPC logic assembly. Swap the DCPQM 1 card with the DCPQM 2 card. Did the fault follow?
- If YES, replace DCPQM 1 card and do close out.
- If NO, continue with next step.
- Remove the DCPQM 1 card and the BATT/RAT Interface card. Perform a continuity check as follows:
From To Result P121A-32 P410A-36 P121A-28 P410A-35 P121C-23 P410A-36 P121C-22 P410A-35 - If there is no continuity, go to step 4.
- If there is continuity, continue with next step.
- Replace the BATT/RAT Interface card.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace the DCPC.
- Do close out.