Message Overview:
Fault Message:
DCPC ETC CONTACTOR-K5 FAILED
Fault Code:
2460427DCP
Associated CAS:
| Reporting LRU: | DC Power Center (DCPC) |
| System Description: | 24-31-00 |
| Schematic Diagram: | 24-61-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-61-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Primary Logic Cards have determined that the Emergency Tie Contactor (ETC) K5 status does not match its commanded state.
Possible Causes:
- Emergency Tie Contactor (ETC) (K5)
- DC Power Center (DCPC) Primary Logic Card (PLC) 1
- DC Power Center (DCPC) Primary Logic Card (PLC) 2
- DC Power Center (DCPC) Primary Logic Card (PLC) 3
- DC Power Center (DCPC) (A63)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the DC Power Center (DCPC) | AMM 24-61-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) | AMM 24-61-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) Primary Logic | AMM 24-61-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) Primary Logic | AMM 24-61-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) L-Series Contactor | AMM 24-61-53-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) L-Series Contactor | AMM 24-61-53-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) Electronic Modules | AMM 24-61-65-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) Electronic Modules | AMM 24-61-65-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Remove power from the A/C.
- Access DCPC ETC K5. Perform a continuity check on K5 as follows:
From To Result K5-B1 K5-B2 K5-7 K5-8 - If there is continuity, go to step 8.
- If there is no continuity, continue with next step.
DCPC ETC CONTACTOR K5 FAIL
- Perform a continuity check as follows:
From To Result K5-8 Ground K5-2 Ground K5-3 Ground - If there is continuity, replace DCPC and do close out.
- If there is no continuity, continue with next step.
- Access the DCPC Logic assembly. Remove PLC 1, 2 and 3. Perform a continuity check between K5 and the PLCs as follows:
From To Result K5-8 P110B-16 K5-8 P210B-16 K5-8 P310B-16 K5-3 P110C-30 K5-3 P210C-30 K5-3 P310C-30 K5-7 Ground - If there is no continuity, replace DCPC and do close out.
- If there is continuity, continue with next step.
- Reconnect any component that was disconnected during troubleshooting. Reinstall PLC 2 and PLC 3 only, leaving PLC 1 removed. Apply power to the A/C. Is the fault still present?
- If NO, replace the PLC 1 and do close out.
- If YES, continue with next step.
- Remove power from the A/C. Remove PLC 2 and reinstall PLC 1. Apply power to the A/C. Is the fault still present?
- If NO, replace the PLC 2 and do close out.
- If YES, continue with next step.
- Remove power from the A/C. Remove PLC 3 and reinstall PLC 2. Apply power to the A/C. Is the fault still present?
- If NO, replace the PLC 3 and do close out.
- If YES, continue with next step.
- Replace K5.
- Do close out.