06/28/19
Message Overview:
Fault Message:
DCPC ETC CURRENT XDCR-IS6 FAILED
Fault Code:
2460467DCP
Associated CAS:
| Reporting LRU: | DC Power Quality Monitor (DCPQM) |
| System Description: | 24-31-00 |
| Schematic Diagram: | 24-31-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-31-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The DC Power Quality Monitor (DCPQM) has detected an Emergency Tie Contactor (ETC) over current while other Transformer Rectifier Units (TRUs) are available and K1 and K2 is open and not failed.
The DCPQM has detected an ETC current near zero while no other TRU power is available and K1 and K2 is ON.
Possible Causes:
- Current Transducer (IS6)
- DC Power Quality Monitor (DCPQM) 1
- DC Power Center (DCPC) (A63)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the DC Power Center (DCPC) | AMM 24-61-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) | AMM 24-61-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) DC Power Quality Monitor | AMM 24-61-13-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) DC Power Quality Monitor | AMM 24-61-13-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the DC Power Center (DCPC) Current Transducers | AMM 24-61-29-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the DC Power Center (DCPC) Current Transducers | AMM 24-61-29-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Active Faults | AMM 45-45-00-970-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Access CAIMS active faults. Is CAIMS message 2460423DCPDCPC TLC1-TTC1 CONTACTOR-K1 FAILED or 2460424DCP DCPC TLC2-TTC2 CONTACTOR-K2 FAILED posted?
- If YES, troubleshoot this message first.
- If NO, continue with next step.
- Access DCPC logic assembly. Swap DCPQM 1 with DCPQM 2. Is the fault resolved?
- If YES, replace DCPQM 1 and do close out.
- If NO, continue with next step.
- Replace current transducer IS6. Is the fault resolved?
- If YES, do close out.
- If NO, continue with next step.
- Replace DCPC.
- Do close out.