09/22/20
Message Overview:
Fault Message:
AVIONICS BAY SMK DET #2 /WRG/DAU 3
Fault Code:
2612248WK
Associated CAS:
| Reporting LRU: | Fire Detection and Extinguishing Control Unit (FIDEEX CU) |
| System Description: | 26-14-00 |
| Schematic Diagram: | 26-14-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 26-10-04 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
This message shows when the Fire Detection and Extinguishing Control Unit (FIDEEX CU) senses that the Avionics Bay Smoke Detector 6 is defective or both the Data Acquisition Unit (DAU) 3 and FIDEEX do not receive the alarm signal.
Possible Causes:
- Fire Detection and Extinguishing Control Unit (FIDEEX CU) (A106)
- Data Acquisition Unit (DAU) 3 (A30)
- Smoke Detector 6 (A221)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-45-0065 - CAIMS Nuisance Fault Messages
Forum Articles/Infoservice/Newsletter: None
NOTE: If both sides (DAU 3 and FIDEEX) are not receiving the alarm, this condition will display an EICAS FAIL message: SMOKE CLOSET FAIL (Amber).
Quick Links:
| Removal of the Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit |
AMM 26-10-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit |
AMM 26-10-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Avionics-Compartment/Avionics Rack Smoke Detectors | AMM 26-14-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Avionics-Compartment/Avionics Rack Smoke Detectors | AMM 26-14-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Measure for 28 VDC at Smoke Detector 6 (A221P1).
- If there is 28 VDC, go to step 4.
- If there is no 28 VDC, continue with next step.
- Perform a wiring check between FIDEEX Control Unit (A106P2) and Smoke Detector 6 (A221P1).
From To Result A221P1-A A106P2-7 A221P1-B A106P2-22 A221P1-C A106P2-38 A221P1-D A106P2-65 A221P1-E Ground - If wiring defects are found, repair defective wiring as required and do close out.
- If no defects are found, continue with next step.
- Replace the FIDEEX Control Unit. Is the fault still present?
- If YES, continue with next step.
- If NO, do close out.
- Perform a wiring check between Smoke Detector 6 (A221P1) and DAU 3 (A30BP1) as follows:
From To Result A221P1-F A30BP1-D11 - If wiring defects are found, repair defective wiring as required and do close out.
- If no defects are found, continue with next step.
- Swap DAU 3 with DAU 4. Is the fault still present?
- If YES, continue with next step.
- If NO, replace defective DAU.
- Replace Smoke Detector 6.
- Do close out.