06/27/19
Message Overview:
Fault Message:
DAU3A 429 / SFCU#1/ WIRING
Fault Code:
2751006STD
Associated CAS:
| Reporting LRU: | Slat/Flap Control Unit (SFCU) |
| System Description: | 27-51-00 |
| Schematic Diagram: | 27-50-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 27-50-07 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-07 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
One of the conditions that follow occurs:
- Slat/Flap Control Unit (SFCU) 1 does not receive input from the Data Acquisition Unit (DAU) 3 Channel A and Channel B.
- The data is invalid.
NOTE: The DAU needs to get both channel failed in order to post this fault.
Possible Causes:
- Data Acquisition Unit (DAU) 3 (A30)
- Slat/Flap Control Unit (SFCU) 1 (A124)
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-45-0065 - CAIMS Nuisance Fault Messages
Forum Articles/Infoservice/Newsletter: None
This fault may be posted due to the SFCU powering up prior to the DAU 4. This fault will clear automatically when the DAU 4 powers up and provides the General purpose ARINC 429 information. Performing a SLAT FLAP RESET on the EMS CDU may clear this fault.
NOTE: Wait at least one minute after SFCU reset to allow self test to run.
Quick Links:
| Removal of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Perform troubleshooting to related systems if the DAU 3 is reporting a fault.
NOTE:- Other LRUs receiving the DAU 3 channel A ARINC 429 inputs are: CPC, SPC, EGPWS, ACSC 1, APU FADEC, BMC 1, and LGECU.
- Other LRUs receiving the DAU 3 channel B ARINC 429 inputs are: CPC, SPC, ACSC 1, APU FADEC, and BMC 1.
- Swap SFCU 1 with SFCU 2.
- If system checks are good, replace SFCU 1 and do close out.
- If fault remains, continue with next step.
- Replace DAU 3.
- Do close out.