06/28/19
Message Overview:
Fault Message:
INVALID SFCU #1 ID/ WIRING
Fault Code:
2751043STD
Associated CAS:
| Reporting LRU: | Slat/Flap Control Unit (SFCU) 1 |
| System Description: | 27-52-00 |
| Schematic Diagram: | 27-50-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 27-50-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Slat/Flap Control Unit (SFCU) 1 pin strapping not valid.
Possible Causes:
- Slat/Flap Control Unit (SFCU) 1 (A124)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap SFCU 1 with SFCU 2 and confirm that they are installed properly and securely.
- If system checks are good, replace SFCU 1 and do close out
- If fault remains, continue with next step
- Verify SFCU 1 pin strapping as per table below:
SFCU PIN STRAPPING PRE SB 700-27-059 (FLAP ZERO TAKE-OFF CAPABILITY):
UNIT TYPE ID0-56 ID1-55 ID2-69 ID3-17 SFCU 1 GX 1 1 SFCU PIN STRAPPING POST SB 700-27-059 (FLAP ZERO TAKE-OFF CAPABILITY):
UNIT TYPE ID0-56 ID1-55 ID2-69 ID3-17 SFCU 1 GX 1 1 - Do close out.