07/03/19
Message Overview:
Fault Message:
DAU4B 429 / SFCU#2/ WIRING
Fault Code:
2752007STD
Associated CAS:
| Reporting LRU: | Slat/Flap Control Unit (SFCU) 2 |
| System Description: | 27-51-00 |
| Schematic Diagram: | 27-50-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 27-50-08 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
One of the conditions that follow occurs:
- The Slat/Flap Control Unit (SFCU) 2 does not receive input from the Data Acquisition Unit (DAU) 4 Channel B
- The data is invalid
NOTE: The DAU needs to get both channel failed in order to post this fault.
Possible Causes:
- Data Acquisition Unit (DAU) 4 (A31)
- Slat Flap Control Unit (SFCU) 2 (A95)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-45-0065 - CAIMS Nuisance Fault Messages
Forum Articles/Infoservice/Newsletter: None
This fault may be posted due to the SFCU powering up prior to the DAU#4. This fault will clear automatically when the DAU#4 powers up and provides the General purpose ARINC 429 information.
Performing a SLAT FLAP RESET on the EMS CDU may clear this fault.
NOTE: Wait at least one minute after SFCU reset to allow self test to run.
Quick Links:
| Removal of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Slat/Flap Control Unit (SFCU) | AMM 27-51-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Perform troubleshooting to related systems if the DAU 4 is reporting a fault.
NOTE:- Other LRU’s receiving the DAU4 channel A ARINC inputs are: CPC 2, SPC CH. B, EGPWS, ACSC 2, EVMU, BMC 2 and LGECU
- Other LRU’s receiving the DAU 4 channel B ARINC inputs are: CPC 2, SPC CH. B, ACSC 2, EVMU and BMC 2
- Swap SFCU 2 with SFCU 1.
- If system checks are good, replace SFCU 2 and do close out.
- If fault remains, continue with next step.
- Replace DAU 4.
- Do close out.