07/12/19
Message Overview:
Fault Message:
LH AFT AC BOOST PUMP ELECT PWR/WRG
Fault Code:
2844606PK
Associated CAS:
| Reporting LRU: | Fuel Management and Quantity Gauging Computer (FMQGC) |
| System Description: | 28-21-00 |
| Schematic Diagram: | 28-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 28-21-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Fuel Management Quantity and Gauging Computer (FMQGC) senses that the Left Wing Aft AC Boost-Pump is not able to go off or on as commanded due to an Electrical Load Management System (LMS) failure.
Possible Causes:
- AC Power Center (ACPC)/Solid-State Power Controller (SSPC) 1 (A2)
- AC Power Center (ACPC) Secondary Logic Card (A7)
- Left Aft AC Boost Pump Cartridge (B7)
- Fuel Management Quantity and Gauging Computer (FMQGC) (A47)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Article/Infoservice/Newsletter: None
NOTE: If both of the CAIMS messages L AFT AC BOOST PUMP/WRG FAULT and L AFT AC BOOST PUMP LMS/WRG FAULT are displayed, troubleshoot with L AFT AC BOOST PUMP/WRG FAULT page first.
Quick Links:
| Electrical/Electronic Safety Precautions | AMM 24-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) Secondary Logic | AMM 24-51-13-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) Secondary Logic | AMM 24-51-13-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) Solid-State Power Controller | AMM 24-51-53-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) Solid-State Power Controller | AMM 24-51-53-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Boost-Pump Cartridges | AMM 28-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Boost-Pump Cartridges | AMM 28-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Boost-Pump Canisters | AMM 28-21-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Boost-Pump Canisters | AMM 28-21-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Computer | AMM 28-41-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Computer | AMM 28-41-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to System Diagnostics | AMM 45-45-00-970-804 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Using the PMAT, access CAIMS, SYSTEM DIAG. Select ATA 24, ACPC A (B), LOAD STATUS LABEL 002, LOAD 1 (L AFT PRI PUMP, Phase A) page. Set the left ENGINE RUN switch to ON and the L PRI PUMPS switch/light to ON (Pushed out). Make sure the result that follows are met:
- If all of the above status are met, go to step 8.
- If one or more of the above status is not met, go to step 3. NOTE: Repeat this step by selecting LABEL 002 Load 2 (L AFT PRI PUMP, Phase B) and LABEL 003 Load 1 (L AFT PRI PUMP, Phase C).
Reference Status LOGIC EQUATION STATE (L TRANSFER REQUEST) ON VIRTUAL CIRCUIT BREAKER (SSPC CIRCUIT BREAKER) IN VIRTUAL SWITCH (SSPC SW) ON LOCK STATE UNLOCKED VOLTAGE STATUS PRESENT CURRENT STATUS FLOWING TRIP STATUS (CIRCUIT BREAKER) NOT TRIP FAIL STATUS (SSPC) NOT FAILED - An alternative way of monitoring the result is to select ACPC IN via EMS CDU1 or CDU2 Signboard Menu:
Left column Center column Label 002 29 28 27 26 25 24 23 22 1 1 1 1 1 1 21 20 19 18 17 16 15 14 1 1 1 1 1 1 Reference L AFT PRIM PUMP Phase B L AFT PRIM PUMP Phase A Label 003 29 28 27 26 25 24 23 22 X X X X X X X X 21 20 19 18 17 16 15 14 1 1 1 1 1 1 Reference L AFT PRIM PUMP Phase C - Built-In Test (BIT) 14 or 22:LOGIC EQUATION STATE (L TRANSFER REQUEST)
- Built-In Test (BIT) 15 or 23:VIRTUAL CIRCUIT BREAKER (SSPC CIRCUIT BREAKER)
- Built-In Test (BIT) 16 or 24:VIRTUAL SWITCH (SSPC SW)
- Built-In Test (BIT) 17 or 25:LOCK STATE
- Built-In Test (BIT) 18 or 26:VOLTAGE STATUS
- Built-In Test (BIT) 19 or 27:CURRENT STATUS
- Built-In Test (BIT) 20 or 28:TRIP STATUS (CIRCUIT BREAKER)
- Built-In Test (BIT) 21 or 29:FAIL STATUS (SSPC)
- If the above status are met, go to step 8.
- If one or more of the above status is not met, continue with next step.
- Perform wiring check (short to ground=fail) between the ACPC (A54P5) and left wing aft AC boost-pump (B7P1).
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Perform a ground check at left wing aft AC boost-pump (B7J1). Repair as required.
- If ground is not present, go to step 6.
- If ground is present, continue with next step.
- Swap the left wing AC boost-pump. Is the fault still present?
- If NO, replace left wing AC boost-pump and do close out.
- If YES, continue with next step.
- Swap the ACPC/SSPC 1 (A2). Is the fault still present?
- If NO, replace ACPC/SSPC 1 (A2) and do close out.
- If YES, continue with next step.
- Swap the ACPC Secondary Logic Card (SLC) (A7). Is the fault still present?
- If NO, replace ACPC Secondary Logic Card (SLC) (A7) and do close out.
- If YES, continue with next step.
- Remove the FMQGC. Re-install the FMQGC making sure it is fully and properly inserted into place. Is the fault still present?
- If NO, do close out.
- If YES, continue with next step.
- Replace FMQGC.
- Do close out.