Message Overview:
Fault Message:
RH CTR XFER PUMP PRESS SW/WRG
Fault Code:
2844622PK
Associated CAS:
| Reporting LRU: | Fuel Management and Quantity Gauging Computer (FMQGC) |
| System Description: | 28-22-00 |
| Schematic Diagram: | 28-22-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 28-22-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
R CNTR TRNS PMP PRES SWITCH/WRG FLT shows on the CAIMS PMAT when both Right Center Transfer-Pump Pressure-Switch status are high or low at the same time.
The Pressure Switch contacts and signals to the Fuel Management Quantity and Gauging Computer (FMQGC) have two status. One is normally shorted to ground and the other is open. They have to be complimentary otherwise the FMQGC will consider the switch failed.
Possible Causes:
- Right Center Transfer-Pump Pressure-Switch (S20)
- Fuel Management and Quantity Gauging Computer (FMQGC) (A47)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Synoptic indication to be confirmed in a simulator or an aircraft.
Quick Links:
| Operational Test of the Center Transfer Pumps | AMM 28-22-00-710-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Center Transfer-Pump Pressure-Switches | AMM 28-22-17-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Center Transfer-Pump Pressure-Switches | AMM 28-22-17-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Computer | AMM 28-41-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Computer | AMM 28-41-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to System Diagnostics | AMM 45-45-00-970-804 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Go to CENTER TRANSFER TEST page via PMAT to turn on Right Center Transfer Pump.
- Check Pump Status/Active Faults data as table below:
Reference Indication Pump Status RIGHT XFER PUMP PRESSURE Not Low (Hi) Active Faults R XFER PRESSURE SWITCH FAIL STATUS Normal - If the pressure is high, go to step 9.
- If the pressure is normal, continue with next step.
- Check pressure switch contacts at connector S20P1 as follows:
From To Expected Result Result S20P1-G S20P1-H Closed S20P1-A S20P1-H Open - If the checks are not good, go to step 9.
- If the checks are good, continue with next step.
- Perform wiring checks as follow:
From To Expected Result Result S20P1-H GS427 Closed S20P1-A Ground Open S20P1-G A47DP1-A12 Closed - If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Turn off Right Center Transfer Pump.
- Check Pump Status/Active Faults data as table below:
Reference Indication Pump Status RIGHT XFER PUMP PRESSURE Low Active Faults R XFER PRESSURE SWITCH FAIL STATUS Normal - If the pressure is low, do close out.
- If the pressure is normal, continue with next step.
- Check pressure switch contacts at connector S20P1 as follows:
From To Expected Result Result S20P1-A S20P1-H Closed S20P1-G S20P1-H Open - If the checks are not good, go to 9.
- If the checks are good, continue with next step.
- Perform wiring checks as follow:
From To Expected Result Result S20P1-H GS427 Closed S20P1-G Ground Open S20P1-A A47DP1-B12 Closed - If wiring checks are good, go to step 10.
- If wiring checks are not good, repair defective wiring as required and do close out.
- Swap right center transfer-pump pressure-switch with left center transfer-pump pressure-switch.
- If system checks are good, replace right center transfer-pump pressure-switch and do close out.
- If fault remains, continue with next step.
- Replace FMQGC.
- Do close out.