Message Overview:
Fault Message:
RVTEXLO 1/WRG/DAU 1
Fault Code:
3141042DAU
Associated CAS:
| Reporting LRU: | Data Acquisition Unit (DAU) 1 |
| System Description: | 27-33-00 31-40-00 |
| Schematic Diagram: | 27-33-00 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 27-33-01 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Data Acquisition Unit (DAU 1) senses that the excitation for the Left Elevator Position Transducer on CH A is out of range.
Possible Causes:
- Left Elevator Position Transducer (MT49)
- Data Acquisition Unit (DAU) 1 (A17)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Connect Electrical Power to the Aircraft | AMM 24-00-00-861-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Remove the Electrical Power from the Aircraft | AMM 24-00-00-861-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Opening of Non-Thermal Circuit Breakers | AMM 24-00-00-863-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Closing of Non-Thermal Circuit Breakers | AMM 24-00-00-863-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Electrical/Electronic Safety Precautions | AMM 24-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Elevator Position Transducers | AMM 27-31-25-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Elevator Position Transducers | AMM 27-31-25-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Active Faults | AMM 45-45-00-970-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to Stored Faults | AMM 45-45-00-970-803 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Lower Trailing-Edge Access-Panels (from 352AB/362AB to 352EB/362EB) |
AMM 55-10-17-000-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Lower Trailing-Edge Access-Panels (from 352AB/362AB to 352EB/362EB) |
AMM 55-10-17-400-802 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Safety Precautions - Maintenance Practices - ALL | SPM 20-00-01-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Remove the DAU 1 to get access to the connector A17AP1 and left elevator position transducer to get access to the connector MT49P1. Perform a continuity check as follows:
From To Result A17AP1-B7 MT49P1-3 A17AP1-C7 MT49P1-2 - If there is no continuity, repair or replace defective wiring as required and do close out.
- If there is continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A17AP1-B7 Ground A17AP1-C7 Ground - If there is continuity, repair or replace defective wiring as required and do close out.
- If there is no continuity, continue with the next step.
- Swap DAU 1 with DAU 3.
- If system checks are good, replace DAU 1 and do close out.
- If fault remains, continue with next step.
- Replace the Left Elevator Position Transducer.
- Do close out.