09/05/19
Message Overview:
Fault Message:
INTERFACE - AIR DATA 1 BUS FAULT
Fault Code:
3440103AE
Associated CAS:
| Reporting LRU: | Enhanced Ground-Proximity Warning System (EGPWS) |
| System Description: | 34-42-00 |
| Schematic Diagram: | 34-42-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 34-41-01 [ Global Express ] [ G5000 ] [ Global XRS ] 34-42-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Loss of communication on ARINC 429 Fault Warning Computer (FWC) bus from Micro Air-Data Computer (MADC) 1 is detected by Enhanced Ground-Proximity Warning System (EGPWS) Computer.
Possible Causes:
- Micro Air-Data Computer (MADC) 1 (A27)
- Enhanced Ground-Proximity Warning System (EGPWS) Computer (A64)
- Junction Box (JB) 3
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter:
- EGPWS Mode 6 Altitude Callout - Navigation-EGPWS-Configuration Strapping for Alternate Mode 6 Aural Altitude Callouts
Quick Links:
| Removal of the Micro Air-Data Computers | AMM 34-11-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Micro Air-Data Computers | AMM 34-11-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Enhanced Ground-Proximity Warning System (EGPWS) Computer |
AMM 34-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Enhanced Ground-Proximity Warning System (EGPWS) Computer |
AMM 34-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Consult EGPWS - NFF reduction before performing the troubleshooting.
- Swap ADC 1 with ADC 2.
- If system checks are good, replace ADC 1 and do close out.
- If fault remains, continue with next step.
- Perform wiring checks between MADC 1, JB3 and EGPWS Computer.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
NOTE: Remove all interface components for short circuit checks.
- Replace EGPWS Computer.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace JB3.
- Do close out.