Message Overview:
Fault Message:
RIGHT BLEED PRESSURE XDCR /WRG
Fault Code:
3616427BMC
Associated CAS:
| Reporting LRU: | Bleed Management Controller (BMC) 2 |
| System Description: | 36-11-00 |
| Schematic Diagram: | 36-11-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 30-11-02 [ Global Express ] [ G5000 ] [ Global XRS ] 36-11-04 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Right Bleed Pressure Transducer (BPT) is not reporting a correct pressure. Inhibited during Take-off and Landing.
Possible Causes:
- Right Bleed Pressure Transducer (MT112)
- Junction Box (JB4)
- Bleed Management Controller (BMC) 2 (A70)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-36-0365 - Bleed management controller - Data Gathering to reduce No Fault Found (NFF) rate
Forum Articles/Infoservice/Newsletter:
- Forum Article 2011-VOL 8 issue 23 - Bleed Management Controller (BMC) Top 10 No Fault Found (NFF) vs. Reliability Improvement Modification Program (RIMP) implementation
- Questionnaire for replacing the BMC. Follow instructions using this (Fill out form)
NOTE: Always verify you are working with the current document revision. Access the CIC website to ensure the latest document revision. - Bleed Pressure can be monitored on the Bleed Synoptic page
- Test Points are available in the Junction Box to monitor the different signals if needed

Quick Links:
| Removal of the Junction Box JB4 | AMM 24-00-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Junction Box JB4 | AMM 24-00-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Bleed Pressure Transducer | AMM 36-11-25-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Bleed Pressure Transducer | AMM 36-11-25-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Bleed Management Controller | AMM 36-11-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Bleed Management Controller | AMM 36-11-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap Right Bleed Pressure Transducer with Left Bleed Pressure Transducer.
- If system checks are good, replace Right Bleed Pressure Transducer and do close out.
- If fault remains, continue with next step.
- Perform wiring checks between BMC 2 and R BPT.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Perform wiring checks between BMC 2 and JB4.
- If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
NOTE: Remove all interface components for short test.
- Swap BMC 2 with BMC 1.
- If system checks are good, replace BMC 2 and do close out.
- If fault remains, continue with next step.
- Replace JB4.
- Do close out.