09/16/19
Message Overview:
Fault Message:
SHORT - EGT SENSOR/CIRCUIT 2 WIRING
Fault Code:
4960155APU
Associated CAS:
| Reporting LRU: | Full-Authority Digital Engine-Controller (FADEC) |
| System Description: | 49-60-00 |
| Schematic Diagram: | 49-61-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 49-61-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Exhaust Gas Temperature (EGT) Sensor 2 conditioning voltage in the Full-Authority Digital Engine-Controller (FADEC) is out of range low but the signal read by the FADEC is in the correct range. This shows a possible short to ground in the EGT Sensor or the engine branched wiring harness.
Possible Causes:
- Exhaust Gas Temperature (EGT) Sensor 2 (TC1-2)
- Auxiliary Power Unit (APU) Full-Authority Digital Engine-Controller (FADEC) (A108)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Servive Bulletin:
- AW700-49-0538 - Auxiliary Power Unit (APU) Exhaust Gas Temperature (EGT) Sensor
- RE220-49-7558 - AIRBORNE AUXILIARY POWER - GAS TURBINE ENGINE - Removal/Replace EGT Sensor, Part No. WE3876282-1 with Part No. WE3876352-1 and Replace/Rework Wiring Harness, Part No. WB3888400-1 with/to part No. WE3888471-1
- RE220-49-8169 - AIRBORNE AUXILIARY POWER - GAS TURBINE ENGINE - Visual Inspection and Sealant Application Method for the Exhaust Gas Temperature (EGT) Sensor, PN WE3876352-1, -2, on RE220 Auxiliary Power Units (APUs)
Forum Articles/Infoservice/Newsletter:
- SIL-APU-87 - AIRBORNE AUXILIARY POWER - GAS TURBINE ENGINE-RE220GX APU Auto Shutdown in Heavy Rain
Quick Links:
| APU Safety Precautions | AMM 49-00-00-910-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Engine Branched Wiring-Harness | AMM 49-12-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Engine Branched Wiring-Harness | AMM 49-12-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Full-Authority Digital Engine-Controller (FADEC) |
AMM 49-61-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Full-Authority Digital Engine-Controller (FADEC) |
AMM 49-61-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Exhaust Gas Temperature (EGT) Sensor | AMM 49-61-05-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Exhaust Gas Temperature (EGT) Sensor | AMM 49-61-05-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Access CAIMS and using active faults, or stored faults find the fault and verify the CAS message. You can use System Diagnostics to view each channel of the APU FADEC (each EGT sensor) in real time, and also access ground faults.
- Inspect the wiring and connectors to the EGT sensor 2 for any damage.
- If defects are found, repair or replace as required and do close out.
- If checks are good, continue with next step.
- Inspect the EGT sensor 2 for condition and check the resistance of EGT sensor 2 (post-to-post) as follows:
From To Expected Result Result Alumel Chromel max 0.5 Ohms - If system checks are good, do close out.
- If fault remains, continue with next step.
- Inspect for RTV sealant per APU Auto Shutdown due to rain RE220-49-8169.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Perform a measurement of the EGT sensor insulation resistance using a Megohmmeter capable of measuring 1 MegaOhm to 1 GigaOhm. Measure from EGT sensor terminal to the EGT sensor flange that attaches to the APU case. The resistance should measure more than 1 MΩ.
- If fault remains, replace the defective or damaged EGT probe. Repair the EGT sensor as per RE220-49-8169 and do close out.
- If system checks are good, continue with next step.
- Re-rack FADEC and verify connector A108BP1-K7 and A108BP1-K8 for damage or FOD. Is the fault still present?
- If NO, do close out.
- If YES, continue with next step.
- Perform wiring checks between APU firewall connector (P802) and EGT sensor 2 terminals as follows:
From To Expected Result Result P802-36 Chromel <5 Ohms P802-37 Alumel <5 Ohms P802-36 Ground Shell Open P802-37 Ground Shell Open Chromel Ground Shell Open Alumel Ground Shell Open - If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Perform wiring checks between APU firewall connector (J802) and the APU FADEC connector (A108BP1) as follows:
From To Expected Result Result J802-36 A108BP1-K7 <11 Ohms J802-37 A108BP1-K8 <11 Ohms J802-36 Ground Shell Open J802-37 Ground Shell Open A108BP1-K7 Ground Shell Open A108BP1-K8 Ground Shell Open - If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace APU FADEC.
- Do close out.